Adjust the DIP and rotary switches according to the table on the
housing.
Sensor Type:
Select the connected sensor type using switches DIP1 to DIP3.
Start Value:
Adjust the number (00 ... 99) using the "Start" rotary switches.
Adjust the factor using the switches DIP4, DIP5.
To obtain a falling curve, adjust a start value which is higher than the
end value.
End Value:
Adjust the number (00 ... 99) using the "End" rotary switches.
Adjust the factor using the DIP6 switch.
Output Signals:
Adjust the output signal using the switches DIP7, DIP8.
Note
Cover the switches with the included self-adhesive polyimide tape
after completion of confi guration.
For information on IrDA interface confi guration, please refer to the
instruction manual for the Paraly ® SW 111 software (accessory).
Configuration using Switches
Start value (rotary switch)
End value (rotary switch)
DIP S1 (from left to right: 1-8)