NORMAL OPERATION / FLAME SENSOR TIMING
The control box has a further function by means of which it is possible to check the correct running of the burner (signal: GREEN LED perma-
nently lit up).
In order to use this function, it is necessary to wait at least ten seconds from the firing up of the burner and press the button of the control box for a mini-
mum of three seconds.
Once the button has been released, the GREEN LED will start to flash, as illustrated in the diagram below.
GREEN LED on
wait at least 10 secs
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will identify the SENSOR TIMING o f the probe from opening of the gas valve, according to the table below.
SIGNAL
1 flash
2 flashes
6 flashes
KIT INTERFACE ADAPTER RMG TO PC Code 3002719
FONCTIONNEMENT NORMAL/ TEMPS DE RÉVÉLATION FLAMME
La boîte de contrôle a une autre fonction qui permet de contrôler si le brûleur fonctionne correctement (signalisation: LED VERT toujours
allumé).
Pour utiliser cette fonction, il faut attendre au moins dix secondes après l'allumage du brûleur et appuyer sur le bouton de la boîte pendant au moins trois
secondes.
Après avoir relâché le bouton, le LED VERT se met à clignoter comme indiqué sur la figure suivante.
VOYANT VERT allumé
attendre au moins 10s
Les impulsions du LED constituent un signal espacé d'environ 3 secondes.
Le nombre d'impulsions indique le TEMPS DE RÉVÉLATION de la sonde dès l'ouverture des vannes gaz, comme d'après le tableau
SIGNAL
1 clignotement
2 clignotements
6 clignotements
KIT INTERFACE ADAPTER RMG TO PC Code 3002719
Press button
for > 3 secs
FLAME SENSOR TIMING
0.4 secs
0.8 secs
2.8 secs
Appuyer sur le bouton
pendant > 3s
TEMPS DE REVELATION FLAMME
0.4 s
0.8 s
2.8 s
Interval
Signal
3 secs
Each time the burner is started up, this information is up-dated
Once the reading has been taken, by pressing the button on the
control box briefly, the burner repeats the start cycle.
WARNING
If a timing of > 2 seconds occurs, delayed start-up is present.
Check the adjustment of the hydraulic brake of the gas valve,
the air damper and the combustion head adjustment.
Intervalle
signal
3s
Cette donnée est mise à jour à chaque démarrage du brûleur.
Après avoir procédé à la lecture, il suffit d'appuyer brièvement
sur le bouton de la boîte de contrôle pour que le brûleur répète
le cycle de démarrage.
ATTENTION
L'allumage est retardé si le temps est >2 s.
Vérifier le réglage du frein hydraulique sur la vanne gaz et le
réglage du volet d'air et de la tête de combustion.
41
GB
Signal
F
signal
suivant..