1. Safety Instructions
This product should be Installed and con-
nected by skilled electricians and ins-
tructed
personnel
in
accordance
IEC/EN 60079-14 and the respective national
legislation on electrical equipment for explo-
sive atmospheres.
The national safety rules and regulations for
the prevention of accidents, as well as the sa-
fety instructions, like this text set in bold-ita-
lics in these operating instructions manual,
shall be observed.
The luminaries must not be operated in Zone
0 or 20 hazardous areas.
The requirements of IEC/EN 60079-31 regar-
ding excessive dust deposits and temperatu-
re must be considered by the user. The indi-
cated surface temperatures are not related to
a layer above 5mm thickness
Before opening, electrical power to the lumi-
naire must be turn off during at least 10mi-
nutes.
The temperature class and explosion group
stated on the luminaire shall be observed. To
ensure adherence to the temperature class
or surface temperature stated on the type la-
bel of the luminaire, the permissible ambient
temperature shall be observed.
Light fi tting shall be used for their intended
purpose and shall be undamaged and in a
perfect and clean conditions.
Keep tightly closed when in operation.
The technical data indicated in point 3 as well
as those indicated in light fi tting, must be ob-
served.
Modifi cations or design changes to this lumi-
naries that can affect the explosion protec-
tion are not permitted.
Avoid multiple, short time switching opera-
tion Only original EATON spare parts may be
used as replacements and for repairs.
Repairs that affect the explosion protection
may only be carried out by
EATON or by a qualifi ed electrician in com-
pliance with the respective national regula-
tions.
Prior to being put into operation, the lumina-
ries shall be checked in accordance with the
instructions as per section 6.
Before initial operation, any foreign matter
shall be removed from light fi tting, do not
keep this operating instructions manual insi-
de of the luminaire during its operation.
2. Conformity with standards
This light fi tting is conform to the standards specifi ed in the EC-Declaration of conformity. It has been
designed, manufactured and tested according to the state of the art and to DIN EN ISO 9001, IEC/
with
EN 80079-34, 94/9 EC: Equipment and protective systems intended for use in potentially explosive
atmospheres. The light fi tting fulfi ll further requirements, such as the EC directive on electromagnetic
compatibility (2004/108/EC).
3. Technical data
Apparatus marking acc. to 94/9/EG and directive:
EC-type examination certifi cate:
Rated voltage:
Electromagnetic ballast (C)
Electronic (E):
Electronic universal (EU)
LED, LED 1E, LED 1EF (direct w/o driver):
Terminals:
Degree of protection IEC/EN 60529:
Insulation class IEC/EN 60598:
Perm. ambient temperature:
Electronic types (E, EU)
Other types (C, LED, LED 1E, LED 1EF)
The Ta range for electronic ballast is reduced up to +40ºC due to their Tw, at higher temperature
EATON cannot guarantee their normal life. When LED tubes are used, the manufactures shall be consulted for their
maximum operating temperature.
Storage temperature in original packaging:
Enclosure material:
Glass material:
Enclosure surface fi nish:
Color of enclosure (standard version):
Dimensions:
Cable entries:
4. Field of application
These accessories are intended for use in potentially explosive atmospheres in Zones 1, 2 in ac-
cordance with IEC/EN 60079-10-1 and in Zones 21,22 in acordance with IEC/EN 60079-10-2. The
enclosure materials used, including any external metal parts, are high quality materials that ensure a
corrosion resistance and resistance to chemical substances according to the requirements for use in
a "normal industrial atmosphere":
- Copper free aluminium alloy casting
- Plastic powder coating fi nish
- Stainless steel
-Borosilicate glass
In case of use in an extremely aggressive atmosphere, please consult to the manufacturer.
5. Use/Properties
This light fi tting can be use inside or outside to illuminate areas with potentially explosive atmosphe-
res, may be used only in places with low mechanical impact risk, due to the normal operation in the
industrial process. The temperature class, explosion group and permissible ambient temperature can
be found in the tables and technical data.
The data according to sections 2 and 4 shall be taken into account during use. Applications other than
those described are not permissible without a written declaration of consent from
Crouse-Hinds.
During operation the instructions stated in section 7 of the operating instructions shall be observed.
The sole responsibility with respect to the suitability and proper use of these luminaries lies with the
operator.
II 2 G Ex d IIB T6...T5 Gb
II 2 G Ex d IIC T6...T5 Gb
II 2 D Ex tb IIIC T58...T93°C Db
See table in Fig. 2 and table 1
LOM 02ATEX2013X
220-230V, 50/60Hz
198-254V, 50/60Hz
175-280 VDC
110-260V, 0, 50/60Hz
T8 up to 277V, 0-50/60Hz
Ask LED tube manufacturer
2x2,5mm2 L y N, 6mm2 PE ext. use ring
terminal, not included
IP 67
I
-20ºC to + 40ºC (E or EU)
-20ºC to + 55ºC
-20ºC to + 55ºC
Aluminium alloy casting (Cu free)
Borosilicate glass
Plastic powder coating
RAL 7032, cover RAL 7016
See Fig. 2
2xM25x1,5 or 2x3/4"NPT one with blanking plug
7/16