Bulkhead lighting fixtures AB 05 Ex-de for hazardous areas Type: GHG 865
1

Technical data

1.1
AB 05 Ex-de GHG 865
EC type examination certificate
(special conditions see
)
X
ATEX - IEC
Category of application acc to 2014/34/EU
IEC Ex Certification of conformity
(special conditions see
)
X
ATEX - IEC
Category of application acc. to IEC Ex
Lamp*
X
ATEX - IEC
*T2
*T3
Protection acc. to IEC/EN 60529
Insulation class to IEC/EN 61140
Rated voltage
Housing material
Protection glas
Ambient temperature:
X
ATEX - IEC
Minimum temperature resistance
-20°C < Ta < + 40°C
Wall assembly entry from below
Ceiling assembly
1)
-20°C < Ta < + 55°C
Wall assembly entry from below
Ceiling assembly
1)
Use heat-resistant cable entries for temperature values above 70°C.
Storage temp. orig packing
Calmping capacity
Cable entrie direct (Ex-d)
Dimensions
Test torque
cover bowl screws M8x40
Cable entries Ex e plastic cable entries from CCH.
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
1 2
(Ø mm / Nm)
Seal 1+2
1 2
(Ø mm / Nm)
Seal 1
1 2
(Ø mm / Nm)
Test torque for screw in thread cable entry (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can vary by using cables with different manufacturing tolerances
and material properties. Please use the combination of sealing 1 + 2 + 3 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any future maintenance work on the cable entry.
When using other cable entries, please observe the relevant remarks.
1.2
Principls
Caution
This symbol warns of a possible failure. Failure to observe this
caution may result in the total failure of the device or the system or
plant to which it is connected.
Note
This symbol highlights important information.
X
Special conditions
ATEX - IEC
This symbol shows Highlights for safe use in accordance to EC-Type-Ex-
amination Certificate/ IEC Ex-Certificate of Conformity.
6
min.
3
(1)(2)
max.
min.
3
(1)(2)
max.
min.
3
(2)
max.
BVS 07 ATEX E 152 X
D II 2 G Ex de IIC T3/T2* Gb
D II 2 D Ex tb IIIC T125 °C Db
IECEx BVS 10.0070X
Ex de II C T3/T2* Gb
Ex tb IIIC T125 °C Db
Light bulb 60 W with lampholder E27
acc IEC/EN 60432-1 / IEC/EN 60064 and DIN 49 810 with T certificate
acc IEC/EN 60064; DIN 49 810 with T certificate
IP 66
I
230 V
aluminium alloy pressure coating grey
Borosilikat
of cables
60°C
60°C
75°C
75°C
-20 °C to +40 °C
4.0 mm²
see ambient temperature
see fig. 2
10 Nm
M20
5.5 / 1.5
7 .0 / 1.0
7.0 / 1.5
9.0 / 1.4
9.5 / 1.0
13.0 / 1.7
2.7
of cable entries
55°C
55°C
70°C
70°C
M25
8.0 / 1.5
10.0 / 2.0
10.0 / 2.3
13.0 / 2.6
13.5 / 1.3
17 .5 / 2.3
3.0
GB