2.2 - MAINS POWER SUPPLY
- E. Alim:  "Mains power supply input"
• Single-phase 230 V (-15% to +20%) 50/60 Hz
• Three-phase 400 V (-15% to +20%) 50/60 Hz
- Current: nominal current of the smoke extraction fan permitted on the box
• Rated operating current for AC3.
• Switch current rating for AC3 = Motor nominal current x 1.5 (pursuant to the decision of 14/04/2002).
- Supply input power (Pa)
Current rating
0.4 A - 2.5 A
Power at 230 V
Power at 400 V
2.3 - OUTPUTS
- Standby position contact:
• Switching voltage: 400 VAC max 47 to 63 Hz or 150 VDC max
• Switching current: 0.1 A to 2 A AC or 0.1 A to 1 A DC
• Holding current: 0.1 A to A AC or 0.1 to 0.5 A DC
- Safety position contact:
• Switching voltage: 400 VAC max 47 to 63 Hz or 150 VDC max
• Switching current: 0.1 A to 2 A AC or 0.1 A to 1 A DC
• Holding current: 0.1 A to A AC or 0.1 to 0.5 A DC
- CMS contact:
• Switching voltage: 400 VAC max 47 to 63 Hz or 150 VDC max
• Switching current: 0.1 A to 2 A AC or 0.1 A to 1 A DC
2.4 - PCB CONSUMPTION: 15 VA

3. ASSEMBLY INSTRUCTIONS

3.1 - REMINDER
In accordance with §8.41 of NF-S-61932, the box must be installed outside the safety zone(s) covered by the fan it controls.
Never drill the base of the box when installing.
This equipment is not suitable for use in locations where there may be children
3.2 - BOX OPERATING CONDITIONS
- Operating temperature: -10 °/+50 °C
- Protection rating: IP54
3.3 - INSTALLING THE BOX
- The box must be mounted vertically against a wall with the cable glands at the bottom; under no circumstances must it be
placed on a sloping wall.
- The fastenings required to attach the box are included. The associated seals must be fitted to ensure the tightness of the
product
- Installation limited to less than 1.5 metres
- To fit the cable glands, refer to the specific installation manual attached.
- To ensure that the box meets its stated specifications, all the cable glands, caps, supplied with each box must be fitted.
- As with any electrical appliance, there must be no water ingress during the installation or wiring phases.
- There must be a free space of at least 15 cm around the box to allow access to the safety buttons on the side of the box.
NT 1920 C - 12/2019
3 A
8 A
800 W
1 kW
2.5 kW
1.4 kW
1.7 kW
4.4 kW
12 A
24 A
43 A
6.7 kW
13.3 kW
23.8 kW
50 A
65 A
100 A
27.7 kW
36 kW
55.4 kW
5