4
Start up
4.1
Configuration
The main menu for adjusting the Multronic can be accessed through operating the ↑-key in
the measuring mask.
Main menu
Select configuration through placing the cursor onto the selected function and operate the
ENTER key.
Configuration menu
Select module configuration through placing the cursor onto the selected item and operate
the ENTER key.
Configuration
module selection
(not available at
Multronic OC!)
The standard signal measuring module that is to be configured can now be selected. To do
so, move the cursor onto the corresponding selected item and operate the ENTER key.
The adjustment of the electrodeless C-measuring module configuration is carried out on
two pages.
Standard signal
configuration page 1
The type of controller can be selected with the control device function.
Value range: Signalling device / 2-pt. PID / 2-pt. fuzzy / 2-pt. aFUZa / 2-pt. aFUZs / 3-pt.
PID / 3-pt. fuzzy / 3-pt. aFUZa / 3-pt. aFUZs
The settings aFUZa and aFUZs relate to adaptive fuzzy controllers that independently
adapt themselves to the control process. aFUZa is an asymptotic fuzzy controller without
overshoots. aFUZs attains the nominal value with a quick algorithm while accepting
overshoots.
417101810_Anhang06_Normsignal.doc
Standard signal measuring module
- 20 -
Rev.: 05-07/10