Télécharger Imprimer la page

salmson SANITSON PREMIUM Instructions De Montage page 14

Publicité

Les langues disponibles

Les langues disponibles

ENGLISH
1. GENERAL REMARKS
Installation and commissioning must only be performed by
qualified staff.
1.1 Application
The SANITSON PREMIUM lifting station is designed for lifting water from
buildings and ground below the sewer system. The SANITSON PRE-
MIUM may therefore be installed either indoors or outdoors.
WARNING! In accordance with standard EN 12056-1 regarding
"Indoor gravity drainage systems", depending on the type of pump,
it is compatible with valve water free from faecal matter (grey water),
valve water containing faecal matter from private dwellings, or rain-
water.
Depending on the type, the SANITSON Premium lifting stations are
compliant with standards 12050-1 or 12050-2 (see table 2).
In the event of non-respect of the use of the components mentioned
below (for a reference of station), the conformity to standards
EN12050-1 / EN12050-2 is not guaranteed and doesn't engage the
responsibility for SALMSON.
Any materials/waste that may prevent the efficient operating of the
pump are prohibited (solids, fibrous materials, tar, sand, cement, ash,
bulky paper, debris, household waste, animal waste, fats, oils, etc.). If
valve water containing fats is produced, a grease-removal tank must
be used.
Always make sure that the indications given in the pump's installation
and commissioning manual are obeyed.
TABLE 1
Total volume (L)
Installation height (mm)
Max authorised water table level from the
bottom of the tank (mm)
TABLE 2
TYPE
PUMP
SANITSON
PREMIUM
Mini-SDL 204-1,5M
200-40
Mini-SDL 204-1,5T4
PREMIUM
SVO205-0,75T4
200-50
SVO206-1,1M
SVO206-1,1T4
SVO206-1,5M
SVO206-1,5T4
SVO206-2,2T4
PREMIUM
Mini-SDL 204-1,5M
400-40
Mini-SDL 204-1,5T4
SVO205-0,75T4
SVO206-1,1M
PREMIUM
SVO206-1,1T4
400-50
SVO206-1,5M
SVO206-1,5T4
SVO206-2,2T4
NF EN 12050-1 : Lifting stations for effluents containing or free from faecal matter.
(1)
When spare parts are ordered, all the information on the nameplate must be included on the order.
without extension
255
1000
500
Voltage
Power
Current
P2
(V)
(kW)
(A)
1~230V
1 X 9,5
3~400V
1 x 1,5
1 X 3,2
3~400V
1 x 0,75
1 x 2
1~230V
1 x 1,1
1 x 6,9
3~400V
1 x 1,1
1 x 3,2
1~230V
1 x 1,5
1 x 9,5
3~400V
1 x 1,5
1 x 3,6
3~400V
1 x 2,2
1 x 4,9
1~230V
2 x 1,5
2 X 9,5
3~400V
2 x 1,5
2 X 3,2
3~400 V
2 x 0,75
2 X 2
1~230 V
2 x 1,1
2 X 6,9
3~400 V
2 x 1,1
2 X 3,2
1~230 V
2 x 1,5
2 X 9,5
3~400 V
2 x 1,5
2 X 3,6
3~400 V
2 x 2,2
2 X 4,9
WARNING! During installation and commissioning, the current stan-
dards and specifications must be strictly observed.
1.2 Technical characteristics
1.2.1 Description
Range
Volume of the tank
Discharge DN
1.2.2 Connection and utility supplies
• Frequency : 50 Hz
• Effluent inlet coupling : ND100
• Ventilation duct coupling : Ø 75
• Maximum inlet flow rate : 15 % of the pump's flow rate at its opera-
ting point
• Maximum instantaneous load on the cover
(buried installation) : 100 kg (vehicles may not drive over and/or
park on the cover)
• Maximum pressure in the discharge duct : 4 bars
• Discharge duct connection (See FIG. 1 to 4)
• Raceway connection : Ø 63
SANITSON PREMIUM 200
with extension
325
1300
1000
Control
Level
unit
detection
temperature
(to order
separatly)
YN3112M
YN3112T4
YN3112T4
YN3112M
YN3112T4
YN3112M
YN3112T4
IPAE
YN3112T4
(0-1mCE)
authorised
YN3212M
for 5 mins
YN3212T4
YN3212T4
YN3212M
YN3212T4
YN3212T4
YN3212M
YN3212T4
14
SANITSON PREMIUM-200-40
SANITSON PREMIUM 400
without extension
with extension
400
1000
500
Max.
Max.
Compliant
fluide
particle
with
size
standard
(°C)
(mm)
6
48
35°C
(60°C
EN 12050-1
(1)
max.)
6
48
470
1300
500
Alarm
signal
available