Below are shown the user menu pages with which it is possible to check the system status and modify
its settings.
Instead on the advanced menu there are the configuration parameters for communication with
MODBUS systems (for further details visit the link: http://www.dabpump.com/evoplus). To leave the
advanced menu you must scroll through all the parameters using the central button.
If the menu pages show a key at bottom left it means that it is not possible to change the settings. To
unblock the menus go to the Home Page and press the hidden button and the button under the key at
the same time until the key disappears.
If no button is pressed for 60 minutes, the settings are automatically blocked and the display
switches off. When any button is pressed the display lights up again and the "Home Page"
appears.
To navigate in the menus, press the central button.
To return to the previous page, hold down the hidden button, then press and release the central button.
To modify the settings use the left and right buttons.
To confirm the change of a setting, hold down the central button "OK" for 3 seconds. Confirmation will
be indicated by the following icon::
Home Page
The main settings of the system are graphically summed up
on the Home Page.
The icon at top left indicates the type of regulation selected.
The icon at centre top indicates the operating mode
selected (auto or economy).
The icon at top right indicates the presence of a single or
twin inverter. The rotation of the icon
or
indicates which circulation pump is operating.
At the centre of the Home Page is a read-only parameter
which can be chosen from a small set of parameters on
Page 9.0 of the menu.
From the Home Page it is possible to access the page for
regulating the contrast of the display: hold down the hidden
button, then press and release the right button.
EVOPLUS circulators offer 2 menus: user menu and
advanced menu. The user menu is accessible from the
Home Page by pressing and releasing the central "Menu"
button.
The user menu is accessible from the Home Page by
holding down the central "Menu" button for 5 seconds.
Page 1.0
Page 2.0
Page 2.0 displays 3 icons which represent:
- central icon = setting currently selected
- right icon = next setting
- left icon = previous setting
Page 3.0
ENGLISH-
The factory settings are set from Page 1.0 by holding down
the left and right buttons at the same time for 3 seconds.
The resetting of the factory settings will be notified by the
appearance of the symbol
next to the word "Default"
The regulating mode is set from Page 2.0. You can choose
between the following modes:
1
= Proportional differential pressure regulation.
2
= Proportional differential pressure regulation
with set-point set by external signal (0-10V or PWM).
3
= Proportional differential pressure regulation with
set-point depending on temperature.
4
= Regulation with constant differential pressure.
5
= Constant differential pressure regulation with
set-point set by external signal (0-10V or PWM).
6
= Constant differential pressure regulation with
set-point depending on temperature.
7
= Regulation with constant curve with rotation speed
set from the display.
8
= Regulation with constant curve with rotation
speed set by an external signal (0-10V or PWM).
The regulating set-point can be modified from Page 3.0.
Depending on the type of regulation chosen on the previous
page, the set-point to be set will be a head or, in the case of
a Constant Curve, a percentage of the rotation speed.