Télécharger Imprimer la page

Weidmüller WAVECONTROL VMR 1ph Notice D'utilisation page 24

Publicité

Les langues disponibles

Les langues disponibles

5.
Electrical connection
WAS5 VMR 1ph
Terminal
1 + reset (18 Vdc...30 Vdc)
2 nc
3 – reset
4 nc
5 Input (24Vac/dc...260Vac/dc)
6 Input (24Vac/dc...260Vac/dc)
7 nc
8 nc
9 nc
10 Relay contact 11
11 Relay contact 12
12 Relay contact 14
Connection cross-section max. 2.5 mm
Multi-wire connection max. 1 mm
(two wires with the same cross-section)
Warning! Please observe that applications with high insulation voltages
require sufficient space or insulation to adjoining devices, as
well as protection against accidental contact. Generally spea-
king, fer rules with plastic collars are to be used.
5.1
Technical Data
Supply voltage
Operating temperature 0 °C ... + 55 °C, VMR 1ph
22
22
WAS2 VMR 3ph
Terminal
1 1 input L1 (200Vac/dc...400 Vac/dc)
2 nc
3 Input L1 (80Vac/dc...250 Vac/dc)
4 Input L2 (80Vac/dc...250 Vac/dc)
5 Input N
6 Input L3 (80Vac/dc...250 Vac/dc)
7 Upper limit value relay contact 11
8 Upper limit value relay contact 12
9 Upper limit value relay contact 14
10 Lower limit value relay contact 21
11 Lower limit value relay contact 22
12 Lower limit value relay contact 24
2
2
18 ... 30 Vdc / approx. 1 W
0 °C ... + 50 °C, VMR 3ph

Publicité