Installation,commissioning
7.3.

inserting the probe

The holder is intended only for mounting probes with a
length of 120 mm.
Make sure the welded area has cooled down before
inserting the probe.
Ensure there is no damage to the probe or the holder.
Check that all o-rings are in place in their appropriate grooves,
and are free of damage.
Insert the seal pusher.
Screw the probe into the PG 13.5 thread at a locking torque
between 2 and 3 Nm.
Type 8200
7.3.1.

operating mode

When a probe is screwed into the direct welding holder, the
seal pusher presses the o-ring into the space between the steel
frame and the probe shaft. This seals the probe in a manner that
almost completely eliminates crevices and their associated risk of
contamination.
When the probe is loosened, the o-ring relaxes again. This lowers
the friction between the o-ring and the other parts of the assembly,
and the process is no longer sealed.
If this takes place while the process is still under pressure, the pressure
evacuation holes feature (see chap. 7.3.2), automatically comes into use.
Sensor tip
Steel mantle
Tip of a direct welding holder
with loose probe: the o-ring is
not under pressure.
Fig. 4:
Tip of a direct welding holder with loose or tightened probe
English
O-ring
Tip of a direct welding holder
with tightened probe: the o-ring,
under pressure, creates a seal
with no crevices.
11