Voltage Supply; Terminating Resistors - JUMO variTRON 500 Notice De Montage

Masquer les pouces Voir aussi pour variTRON 500:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3 Electrical connection
Connection
Designa-
tion
Serial interface
Com1,
RS232
Com2
(optional)
Serial interface
Com1,
RS485
Com2
(optional)
3.3.3

Voltage supply

Connection
Designa-
tion
Voltage supply In +24 V and
GND
3.3.4

Terminating resistors

The internal terminating resistors for the Com1 and Com2 interfaces are only available for RS485.
The terminating resistors are deactivated per default. To activate them, switches 1 and 2 for the relevant
interface must be closed.
NOTE!
To ensure fault-free operation, terminating resistors are required at the beginning and end of an RS485
transmission path.
24
Num-
Connection element
ber
(11),
(9)
(11),
(9)
Num-
Symbol and terminal designation
ber
(6)
+
U
-
332
120
332
Assignment
2 RxD
3 TxD
5 GND
3 TxD+/RxD+
5 GND
8 TxD-/RxD-
+24 V
x
GND
+5 V
?
3
1
?
8
2
?
GND
Received data
Transmission data
Ground
Transmission/received data
+
Ground
Transmission/received data -