Module Modbus RTU
8 READ/WRITE MODBUS DATA REGISTER
Designation
Modbus Slave ID
Update rate
Baud rate
Data bits
Parity
Stop bits
Enable Periodical Log 0
data
9 CODES AND UNITS TABLE
Code
Name
Code
0
None
10
1
mWh
11
2
Wh
12
3
kWh
13
4
MWh
14
5
GWh
15
6
J
16
7
kJ
17
8
MJ
18
9
GJ
19
10 ERROR CODES MEANING
Only one error is shown at the time by priority.
Description
No error
No communication with the meter
Basic parameter error in flash or RAM
Defective primary voltage (only if mains unit used)
-> Supply from backup battery
Hardware error of US measurement
-> Transducer defective or short-circuit
Temperature range exceeds [-9.9°C - 190 °C]
-> Sensor short-circuit or sensor break
Modbus
Registr
Modbus
Register
e Type
Address
41001
Holding
1000
41002
Holding
1001
41003
Holding
1002
41005
Holding
1004
41006
Holding
1005
41007
Holding
1006
41008
Holding
1007
Name
Code
Name
cal
20
m
3
kcal
21
mGal
Mcal
22
Gal
Gcal
23
kGal
Btu
24
MGal
kBtu
25
ml/h
MBtu
26
l/h
GBtu
27
m
3
/h
ml
28
mGal/min
l
29
Gal/min
Date
Default
Possible values
value
Value
Range
0xHHLL
UInt16
0x0101
pour lequel HH = 0x01 ou
0x00 LL = 0x01 - 0xF7
UInt16
150
0 - 65535
1200, 2400, 4800, 9600,
UInt32
9600
14400, 19200, 38400,
56000, 57600, 115200
UInt16
8
8
110 ('n'), 111 ('o'),
1 char
78 ('N')
101 ('e'), 78 ('N'), 79 ('O'),
ASCII
69 ('E')
UInt16
1
1, 2
Uint16
0
0, 1
Code
Name
30
kGal/min
31
MGal/min
32
mW
33
W
34
kW
35
MW
36
GW
37
Btu/h
38
kBtu/h
39
MBtu/h
Error Code value in
Error code of
30165 or 40165
the meter
Modbus Register
-
0x00 00
-
0x01 00
C-1
0x00 08
E-8
0x00 04
E-4
0x00 28
E-1
0x00 50
8
Code
Name
40
GBtu/h
41
°C
42
°F
Priority
-
1
2
3
4
5