Module Modbus RTU
Designation
Power (Unit ID)
Power (Float)
Flow
Flow (Unit factor)
Flow (Unit name)
Flow (Unit ID)
Flow (Float)
Forward temperature
Forward temperature (Unit name)
Forward temperature (Unit ID)
Forward temperature (Float)
Return temperature
Return temperature (Unit name)
Return temperature (Unit ID)
Return temperature (Float)
Temperature difference
Temperature difference (Unit name)
Temperature difference (Unit ID)
Temperature difference (Float)
Tariff Energy 1
Tariff Energy 1 (Unit factor)
Tariff Energy 1 (Unit name)
Tariff Energy 1 (Unit ID)
Tariff Energy 1 (Float)
Tariff Volume 1
Tariff Volume 1 (Unit factor)
Tariff Volume 1 (Unit name)
Tariff Volume 1 (Unit ID)
Tariff Volume 1 (Float)
Tariff Energy 2
Tariff Energy 2 (Unit factor)
Tariff Energy 2 (Unit name)
Tariff Energy 2 (Unit ID)
Tariff Energy 2 (Float)
Tariff Volume 2
Tariff Volume 2 (Unit factor)
Tariff Volume 2 (Unit name)
Tariff Volume 2 (Unit ID)
Tariff Volume 2 (Float)
Tariff Energy 3
Tariff Energy 3 (Unit factor)
Tariff Energy 3 (Unit name)
Tariff Energy 3 (Unit ID)
Tariff Energy 3 (Float)
Tariff Volume 3
Modbus
Modbus
Register
Register Type
30028 or 40028
Input or Holding
30029 or 40029
Input or Holding
30031 or 40031
Input or Holding
30033 or 40033
Input or Holding
30034 or 40034
Input or Holding
30038 or 40038
Input or Holding
30039 or 40039
Input or Holding
30041 or 40041
Input or Holding
30042 or 40042
Input or Holding
30046 or 40046
Input or Holding
30047 or 40047
Input or Holding
30049 or 40049
Input or Holding
30050 or 40050
Input or Holding
30054 or 40054
Input or Holding
30055 or 40055
Input or Holding
30057 or 40057
Input or Holding
30058 or 40058
Input or Holding
30062 or 40062
Input or Holding
30063 or 40063
Input or Holding
30065 or 40065
Input or Holding
30067 or 40067
Input or Holding
30068 or 40068
Input or Holding
30072 or 40072
Input or Holding
30073 or 40073
Input or Holding
30075 or 40075
Input or Holding
30077 or 40077
Input or Holding
30078 or 40078
Input or Holding
30082 or 40082
Input or Holding
30083 or 40083
Input or Holding
30085 or 40085
Input or Holding
30087 or 40087
Input or Holding
30088 or 40088
Input or Holding
30092 or 40092
Input or Holding
30093 or 40093
Input or Holding
30095 or 40095
Input or Holding
30097 or 40097
Input or Holding
30098 or 40098
Input or Holding
30102 or 40102
Input or Holding
30103 or 40103
Input or Holding
30105 or 40105
Input or Holding
30107 or 40107
Input or Holding
30108 or 40108
Input or Holding
30112 or 40112
Input or Holding
30113 or 40113
Input or Holding
30115 or 40115
Input or Holding
6
Modbus
Data Value
Address
Range
27
UInt16
28
IEEE 754
30
Int32
32
UInt16
33
8 char ASCII
37
UInt16
38
IEEE 754
40
Int16
41
8 char ASCII
45
UInt16
46
IEEE 754
48
Int16
49
8 char ASCII
53
UInt16
54
IEEE 754
56
Int16
57
8 char ASCII
61
UInt16
62
IEEE 754
64
Int32
66
UInt16
67
8 char ASCII
71
UInt16
72
IEEE 754
74
Int32
76
UInt16
77
8 char ASCII
81
UInt16
82
IEEE 754
84
Int32
86
UInt16
87
8 char ASCII
91
UInt16
92
IEEE 754
94
Int32
96
UInt16
97
8 char ASCII
101
UInt16
102
IEEE 754
104
Int32
106
UInt16
107
8 char ASCII
111
UInt16
112
IEEE 754
114
Int32
04/2019