Building time con-
stant
64
Quick setback
65
Room temperature
source
66
Type of optimization
67
Maximum heating
up time
68
Maximum optimum
shutdown
69
Maximum limitation
of room temperature
70
Effect of room tem-
perature
Building Technologies
20 h
(0...50)
......................
1
(0 / 1)
.........................
A
(0 / 1 / 2 / 3 / A)
.........................
0
(0 / 1)
.........................
00:00 h
(00:00...42:00)
......................
0:00 h
(0:00...6:00)
......................
--.- °C
(--.- / 0...35)
...................
4
(0...20)
.........................
74 319 0618 0 a
Light = 10 h
Medium = 25 h
h
Heavy = 50 h
0 = no quick setback
1 = quick setback
0 = no room temperature sen-
sor present
1 = room unit at terminal A6
2 = room temperature sensor at
terminal B5
3 = mean value of the 2 units at
terminals A6 and B5
A = automatic selection
0 = optimization with room
model
1 = optimization with room unit /
room temperature sensor
(setting 0 only allows optimum
start control)
Maximum forward shift for
switching on before occupancy
h
starts
Setting 00:00 = no optimum
start control
Maximum forward shift for
switching off before occupancy
h
ends
Setting 0:00 = no optimum stop
control
Setting --.- = limitation deacti-
vated
°C
Function only possible with
room unit / room temperature
sensor
Gain factor for effect of room
temperature
Function only possible with
room unit / room temperature
sensor