Alarm
A46
Description
This alarm is only active on PARALLEL systems. Continuity is not ensured
in the event of a fault on one of the UPS units.
Possible
The total load is higher than the maximum expected value.
causes
Possible failure on the measuring circuit.
Solutions
1. Check the load fed by the system.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A47
Description
Internal error.
Possible
Microcontroller communication problems.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A48
Description
Internal error.
Possible
Microcontroller communication problems.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A49
Description
Internal error.
Possible
Microcontroller communication problems.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A51
Description
The battery temperature is out of tolerance. This alarm is only active when
the temperature probe is installed and enabled on the battery.
Possible
Anomalous temperature in the battery cabinet.
causes
Possible failure on the measuring circuit.
Solutions
1. Check the temperature on the batteries and remove the cause of the
alarm, if any.
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
PAR LOST REDUND
SEND PARAM ERROR
RCV PARAM ERROR
TEST MODE ERROR
BATT TEMPERATURE
UPS user manual
Utilizzo dell'UPS
OMG38225 REV.F
57