Installation and Operating Instructions

TEST AND MAINTENANCE PLAN

Folgendes ist zu prüfen:
Interval
Test and maintenance work
Test run up to maximum nominal speed
1/2 annual
and then deactivate again
Check fan and drive motor for running noises.
1/2 annual
Test run for at least 20 minutes and then deactivate
again.
For fans with bearing condition diagnostics, operate fan
Annual
until steady-state is reached (around 60-75 minutes) be-
fore reading out values
(see Installation and Operating Instructions for LZD).
General visual inspection and check of fan condition for
external soiling, correct fastening, corrosion and dama-
Annual
ge.
Clean components for functional integrity if needed.
Check fan suspension and on-site substructure/foun-
dation for damage and corrosion as well as correct
Annual
fastening.
Check flexible connectors and connections for tensi-
on-free installation, tightness, correct fastening, soiling
Annual
and damage.
Clean components for functional integrity if needed.
Check vibration dampers for functionality, correct fas-
Annual
tening, corrosion and damage.
Check air gap between wingtip and fan casing.
Annual
Check drive motor for soiling, corrosion, damage and
correct fastening. Clean components for functional inte-
Annual
grity if needed.
Check impeller for soiling, corrosion, damage and cor-
rect fastening.
Annual
Clean components for functional integrity if needed.
Check inspection opening for tight fit, corrosion and
Annual
damage.
Check protection devices (protection grilles, etc.) for so-
iling, corrosion, damage and correct fastening.
Annual
Clean components for functional integrity if needed.
Check accessory components (mounting brackets,
backdraught shutters, extension ducts, etc.) for soiling,
corrosion, damage and correct fastening.
Annual
Clean components for functional integrity if needed.
Check terminax box (motor and casing terminal box)
and connection cable for correct fit, damage and cor-
Annual
rosion.
Check power consumption of drive motor
Annual
Check motor protection device, for ventilation mode
Annual
(motor protection device, not in case of fire).
Check on-site bridging of frequency converter and mo-
Annual
tor protection devices in case of fire.
Measurement and evaluation of bearing conditions with
Annual
bearing condition diagnostics.
Check fan vibration state
Annual
Check impeller for imbalance
Annual
Meduim-Pressure Axial Smoke Extraction Fans – B AMD F300/F400
Standard
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
21
Fan
incl . LZD Basic
incl . LZD Comfort
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
EN
To be carried out by:
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Specialist personnel
Specialist personnel

Publicité

Table des Matières
loading

Table des Matières