Start-Up And Configuration; Climate Related Curves - HTW A60CGN8PLUS Manuel De L'utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1. when EVU signal is on, the unit operate as below:
DHW mode turn on, the setting temperature will be changed to 70℃
automatically, and the TBH operate as below:T5<69. the TBH is on,
T5 ≥ 70, the TBH is off. The unit operate in cooling/heating mode
as the normal logic.

9 START-UP AND CONFIGURATION

The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and
user expertise.
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as
applicable.

9.1 Climate related curves

The climate related curves can be selected in the user interface. Once the curve is selected, the target water flow temperature
in each mode is calculated by the curve.
It's possible to select curves even dual room thermostat function is enabled.
The relationship between outdoor temperature (T4/°C) and the target water temperature(T1S/°C) is described in the tables and
pictures. )
Temperature curves for heating mode and ECO heating mode
≤ - 20
T4
- 19
- 18
1- T1S
38
38
38
2- T1S
37
37
37
3- T1S
36
36
36
4- T1S
35
35
35
5- T1S
34
34
34
6- T1S
32
32
32
7- T1S
31
31
31
8- T1S
29
29
29
T4
1
2
3
1- T1S
35
35
34
2- T1S
34
34
33
3- T1S
32
32
32
4- T1S
31
31
31
5- T1S
30
30
30
6- T1S
29
29
29
7- T1S
28
28
28
8- T1S
26
26
26
The automatic setting curve
The automatic setting curve is the ninth curve,the ninth curve can be set as following:
T1SETH1
T1SETH2
State:In the setting the wired controller, if T4H2<T4H1, then exchange their value; if T1SETH1<T1SETH2, then
exchange their value.
CAUTION
- 17
- 16
- 15
- 14
- 13
38
38
37
37
37
37
37
36
36
36
35
35
35
35
35
34
34
34
34
34
33
33
33
33
33
32
31
31
31
31
31
30
30
30
30
29
28
28
28
28
4
5
6
7
8
34
34
34
34
34
33
33
33
33
33
32
32
32
31
31
31
31
31
30
30
30
30
30
29
29
29
29
29
28
28
28
28
28
27
27
26
26
26
26
25
T1S (T1S2)
T4H1
T4H2
2. When EVU signal is off, and SG signal is on, the unit operate
normally.
3. When EVU signal is off, SG signal is off, the DHW mode is off, and
the TBH is invalid, disinfect function is invalid. The max running time for
cooling/heating is "SG RUNNIN TIME", then unit will be off.
- 12
- 11
- 10
- 9
- 8
- 7
37
37
37
36
36
36
36
36
36
35
35
35
35
34
34
34
34
34
34
33
33
33
33
33
33
32
32
32
32
32
31
31
31
31
30
30
30
30
30
30
29
29
28
28
28
28
27
27
9
10
11
12
13
14
33
33
33
33
33
33
32
32
32
32
32
32
31
31
31
31
30
30
30
30
30
30
29
29
29
29
29
29
28
28
28
28
28
28
27
27
27
27
27
27
26
26
25
25
25
25
25
25
T4
42
- 6
- 5
- 4
- 3
- 2
- 1
36
36
36
35
35
35
35
35
35
34
34
34
34
33
33
33
33
33
33
32
32
32
32
32
32
31
31
31
31
31
30
30
30
30
30
30
29
29
29
29
29
29
27
27
27
27
27
27
≥ 20
15
16
17
18
19
32
32
32
32
32
32
31
31
31
31
31
31
30
30
30
30
29
29
29
29
29
29
28
28
28
28
28
28
27
27
27
27
27
27
26
26
26
26
26
26
25
25
25
24
24
24
24
24
0
35
34
33
32
31
29
28
26
32
31
29
28
27
26
25
24

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

A100cgn8plusA160cgn8plus

Table des Matières