Technical Data; General Data And Operating Conditions - Lenze L-force Drives 9400 Instructions De Montage

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

3

Technical data

3.1

General data and operating conditions

Supply system data
Supply forms
Noise emission
Noise immunity
Conformity and approval
Conformity
CE
Conformity
CE
EAC
EAC
Approval
UL
C
US
Protection of persons and devices
Enclosure
Insulation resistance
Insulation of control
circuits
Short−circuit strength
Motor − protective
measures against
Discharge current
Cyclic mains switching
EDK94ASH24 DE/EN/FR/ES/IT 5.0
General data and operating conditions
With earthed neutral Unrestricted use
IT systems
Observe instructions about special measures!
EN 61800−3
Cable−guided, up to 10 m motor cable length: category C2
Radiation: category C3
EN 61800−3
Category C3
2006/95/EC
Low−Voltage Directive
2004/108/EC
EMC Directive
TP TC 004/2011
On safety of low voltage
equipment
(TR CU 004/2011)
TP TC 020/2011
Electromagnetic
compatibility of technical
(TR CU 020/2011)
means
UL 508C
Power Conversion Equipment
(File No. E132659) for USA
CSA C22.2 No. 14−13
Power Conversion Equipment
(File No. E132659) for Canada
EN 60529
IP 20
NEMA 250
Protection against contact in
accordance with type 1
EN 61800−5−1
Overvoltage category III
Reduction from 2000 m amsl onwards: Overvoltage category
II
EN 61800−5−1
Safe mains isolation by double/reinforced insulation for
mains with neutral earthing with a rated voltage for the
external conductor/star point up to 300 V.
EN 61800−5−1
Motor connection: with restrictions, error acknowledgement
required
Control connections: without restrictions
l
Short circuit
l
Earth fault
l
Overvoltage
l
Motor stalling
l
Motor overtemperature
(PTC or thermal contact, I
EN 61800−5−1
> 3.5 mA AC, > 10 mA DC
Cyclic mains switching of 5 times in 5 minutes is permissible
without restrictions.
l
Technical data
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Not in the wire range of
the terminals on the
motor side
2
t monitoring)
Observe regulations and
safety instructions!
3
49