6.5. By-pass adjustment: For it to work correctly, it must be selected according to the average flow of the inner unit and must be installed on the outlet
of the machine to avoid direct discharge from the fan.
Position the counterweight on the end furthest away from the flap or the shaft. Move the
weight inwards or towards the shaft until the flap opens and the air speed inside the
diffusion element is equal to or below 4 m/s or, until the passing of air does not product
noise on this part.
The closer the counterweight is to the flap, the greater the by-pass flow and the further
away it is the lesser the by-pass air flow. The rod and counterweight can be removed if
required.
7.
MOST FREQUENT ERRORS
ERROR
When the centre is powered by 230
1
VAC, the display does not light up.
The display indicates an error
2
S1, S11, S12
S3, S31, S32
5 min after switching the centre on,
3
the display shows the letter E in all
zones and all grilles are closed.
The letter E lights up in a zone and
4
the grilles in this zone are closed.
The display shows no error but the
5
equipment does not respond
The equipment gives out cold and
should give out heat
6
(and vice versa). Or only gives out
one of the two
When the damper should
7
open  close
(and vice versa).
8
One of the grilles does not work.
All of the dampers work properly but
9
the air conditioning equipment does
not work.
The equipment switches on and of
with the MASTER at a standstill or
10
some zones close or open without
any signal from the thermostat.

TECHNICAL CHARACTERISTICS:

Control board (receiver)
 Power: 230 VAC, 50/60 Hz.
 Consumption: 14 VA
 6 relay outputs. Maximum current load: 6 A .Cos =1
 Average scope: 50 m in free field. 20 m in the habitat.
 External aiming antena.
 Size (mm): 160 x 90 x 60
 Carrier frequency (ISM Band, as per I-ETS 300-220 standard): 433.92
MHz (Optional: 434.33 MHz)
 Operating cycle <10%
 Recieverr. Class III
 Protection level: IP 20
 Electric shock insulation Clase II.
 Operating temperature: 0 ºC a 55ºC.
 Storage temperature:: -10 ºC a 60 ºC.
Hereby MADEL ATD decalres that the KRCPLUS is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/CE.
http://www.madel.com/esp/pdf/Zoningconformidadkrcplus.pdf
INDICATOR
CAUSE
Lack of
Sensor error
Incorrect configuration
Bad communication
Time programming
Bad 4 way valve
connection
Motors badly connected
Zone regulator connection
Air conditioning
equipment badly
connected
Interference with
neighbouring installations
Thermostat (transmiter)
Check that voltage reaches the centre (230
VAC 10%).
voltage
 Error S1: Connect S1 air sensor
 Error S11: Return sensor > 40ºC
 Error S12: Return sensor < 6ºC
 Error S3: Connect S3 water sensor
 Error S31: Water sensor <5ºC
 Error S32: Water sensor >45ºC
 Check thermostat configuration.
 Antenna not receiving. Modify position.
 The zone is
thermostat SETUP.
 Interference in the communication. Modify
thermostat location.
 Thermostat battery low
 Check that no programming is enabled on
the thermostat and that the time is for the
equipment to be switched off.
 The 4-way valve is badly connected or badly
configured. See Sect. 2.2.1.2.
 The 4-way valve is not connected.
 Check the motor connection.
Polarity (black -, red +)
 Check the motor connection.
Polarity (black -, red +)
 Check that the regulator is not obstructed.
 Check the configuration of the control centre
depending on the machine type.
 Check the equipment connection to the
board.
 Check that there are no two thermostats with
the same configuration.
 Check whether there is some other Zoning
System with the same series number
installed in the neighbouring households
(0.03% probability)
 Power: 2 x 1.5 V LR06 AA batteries (supplied). Average autonomy 1 year
(or more).
 Battery wear indicator.
 Carrier frequency (ISM Band, as per I-ETS 300-220 standard): 433.92
MHz (Optional: 434.33 MHz)
 Average scope: 50 m in free field. 20 m in the habitat.
 Size (mm) (mm): 112 x 71 x 19.
 Operating temperature: 0 ºC a 55ºC.
 Storage temperature:: -10 ºC a 60 ºC..
 Wall attachment using screws (supplied)
 Protection level: IP 20
ordered temp. variation of  3ºC
 ECO mode (
ENGLISH
SOLUTION
badly configured in the
)