6.
MOST FREQUENT ERRORS
ERROR
When the centre is powered
1
by 230 VAC, any led light up.
The right red led flashes
2
quickly.
(Zoning type installation)
5 min after switching the
centre on, the zone leds
3
flashes in all zones and all
grilles are closed.
Some of the zone led flashes
4
and the damper in this zone
is closed.
When the damper should
open close
5
(And vice versa).
One of the dampers does
6
not work.
All of the dampers work
properly but the air
7
conditioning equipment does
not work.
TECHNICAL CHARACTERISTICS:
Control board
Power: 230 VAC, 50/60 Hz.
Power consumption: 4 VA
2 relay outputs. Maximum current load: 6 A .Cos
Size (mm): 105 x 90 x 60
Protection level: IP 20
Electric shock insulation Clase II.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC.
Hereby MADEL ATD decalres that the Kca (control board + thermostat) is in compliance with the essential requirements and other
relevant provisions of Directive 1999/5/CE.
INDICADOR
configuration or
communication
Zone regulator
Air conditioning
equipment badly
=1
http://www.madel.com/esp/pdf/Zoningconformidadkca.pdf
CAUSA
Lack of
Check that voltage reaches the
centre (230 VAC 10%).
voltage
Connect the sound or leave the
Sensor error
resistance
default.
Incorrect
Check thermostat configuration.
Invert the bus polarity
incorret bus
wiring
The zone is badly configured in the
Bad
thermostat SETUP.
Thermostat battery low
Check the motor connection.
Motors badly
connected
Polarity (black -, red +)
Check the motor connection.
Polarity (black -, red +)
Check that the regulator is not
connection
obstructed.
Check the Sw1 configuration of the
control centre depending on the
machine type.
connected
Check the equipment connection
to the board.
Thermostat
Power: 2 x 1.5 V LR06 AA batteries (supplied). Average
autonomy 1 year (or more).
Battery wear indicator.
Size (mm) (mm): 112 x 71 x 19.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC..
Wall attachment using screws (supplied)
Protection level: IP 20
ECO mode (ordered temp. variation of 3ºC)