NOTE: The first time batteries are inserted, the configuration menu is directly accessed. Where configuration is not automatically accessed or where it is to be modified,
enter SETUP mode (with the thermostat on) by pressing the combination of buttons shown in the figure. Then follow the same steps 1 to 4 as in the previous figure.
5.
CONFIGURATION TEST: Before starting up the equipment, it is wise to check the configuration between the
thermostats and the control centre to make sure the thermostats communicate correctly. The grilles do not yet have to be
checked, only the radio communications.
5.1. Place all thermostats in the corresponding zone and aim the control centre antenna towards the zone where the thermostats are furthest away.
Power the control centre to 230 VAC (Wait approx. 2 min. for the centre to carry out its opening cycle.
1
Switch on the MASTER thermostat and switch to cold at 15 ºC
Start the zone thermostats and set to 15ºC, check that the
2
Select 35ºC on each thermostat, check that the display shows
3
Repeat the raising and lowering temperature operation and
4
check that the indicator changes from O to X and vice versa.
If there is no communication after 5 min, the indicator will display the letter E. In this case, check that the series number
5
programmed in the thermostat corresponds to that of the KRCPLUS control panel. If it is properly configured, change the location of
the thermostat in the room or re-aim the antenna.
6.
START-UP
6.1. Connect the air handling unit (AHU) using the diagram supplied..
6.2. Power the control centre to 230 VAC. The centre will implement the opening cycle. All the grilles will open first and, once the mode has been
detected, they are all closed and work started depending on the temperatures selected in the thermostats..
6.3. Check that all zones work properly in line with the table below:
Switch on the MASTER thermostat, switch to
1
cold at 15 ºC
Start the zone thermostats and set to 15ºC,
2
check that the corresponding damper opens
on each one.
Wait for the AHU to start up and check that
3
cold is produced.
Select 35ºC on each thermostat, check that the
4
corresponding grille closes and that the
machine stops when the last one is closed
(1) Heat Pump only. (2) For Electronic + Single-Zone heating configuration only
2. Select Crono mode (+/-)
1. Enter SET-UP mode
2. Insert ID number
See ID nubmer in the lable of the control panel
display shows all zones open
(indicator O)
all zones closed
(Indicator X)
Switch on the MASTER thermostat, switch to
Start the zone thermostats and set to 35ºC,
check that the corresponding damper opens
Wait for the AHU to start up and check that
Select 15ºC on each thermostat, check that the
corresponding grille closes and that the
machine stops when the last one is closed
3. Insert ID number
See ID nubmer in the lable of the control panel
3. Select zone number
Switch on the MASTER thermostat and switch to heat at 35 ºC
Start the zone thermostats and set to 35ºC, check that the
display shows all zones open
(indicator O)
Select 15ºC on each thermostat, check that the display shows
all zones closed
Repeat the raising and lowering temperature operation and
check that the indicator changes from O to X and vice versa.
(1. Heat pump only)
heat at 35 ºC
on each one
heat is produced.
4. Select zone number
(Indicator X)
(2. Configuration Electronic + single heating )
Switch on the MASTER thermostat, switch to
boiler at 35 ºC
Check that the boiler and the V relay on the
control centre are enabled..
Select 15ºC on the MASTER control and check
that the boiler switches off
-
ENGLISH