Cable Connection; Shielding And Cable Routing - Balluff BTL7-S5-M-BE/BF/CE/ZE/ZF-S32/S115 Série Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

BTL7-S5 _ _ ( _ )-M _ _ _ _ -BE/BF/CE/ZE/ZF-S32/S115/KA _ _ /FA _ _
Magnetostrictive Linear Position Sensor — Rod Style
4
Installation and connection (continued)
4.4.3

Cable connection

BTL7 standard
Wire
BTL7-S5_ _...-KA
color
BTL7-S5_ _...-FA
YE yellow
+Clk
GY gray
+Data
PK pink
–Clk
RD red
Not used
1)
GN green
–Data
BU blue
GND
BN brown 10...30 V
WH white
Not used
1)
Unassigned leads can be connected to the GND on the controller side
1)
but not to the shield.
Communication line
2)
Tab. 4-4:
Connection assignment BTL7... cable
Clk, Data and supply are twisted in pairs (see
Fig. 4-12).
+Clk
–Clk
+Data
–Data
GND
BTL7...-
+24 V
cable
Fig. 4-12:
Connection example for BTL7-S...-cable 24 V DC with
evaluation/controller
12
english
BTL7 USB
configurable
BTL7-S510...-KA
BTL7-S510...-FA
+Clk
+Data
–Clk
La
2)
–Data
GND
10...30 V
Lb
2)
YE
PK
GY
GN
BU
Evaluation or
BN
controller
4.5

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the BTL and controller using a shielded cable.
Shielding: Copper filament braided, at least 85%
coverage
Connector version: Shield is interally connected to
connector housing.
Cable version: On the BTL side the cable shielding is
connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL, holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-S...
Max. 500 m
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields. Required cable cross-section ≥ 0.6 mm
≤ AWG19.
Tab. 4-5:
Cable length BTL7
For notes on cable length, see Technical data
on page 20, Fig. 8-2.
1)
or
2

Publicité

Table des Matières
loading

Table des Matières