4.3.
E

QUIPMENT REPAIRS

Disconnect the battery charger from the AC power network and disconnect the batteries before undertaking
any repairs.
When fuses have blown, only use fuses of the type and size recommended in this manual.
Please contact a reseller or CRISTEC for any other repairs.
5.

TECHNICAL SPECIFICATIONS

Models
Input
Voltage
Output power from 85 to 170Vac
Frequency
Current intensity 230/115Vac
Power factor
Efficiency
Input fuses
Sortie
Number of outputs
Total rated current (+/-7%) / Rated power
Load curve
Type of batteries
Regulated and filtered output voltage
Regulation tolerance before distributors
and fuses
Peak-to-peak ripple and noise
Output fuses mounted in the BAT pole -
Environment
Operating temperature
Cooling
Relative humidity
Storage temperature
Casing
Material
Paintwork
Dimensions excluding cable gland (length,
height, depth) / Weight
Fixing centre distances
Fixing screw (wall)
Protection factor
Board protection
Standards
CE/EMC marking
CE/safety marking
Electrical protections
CPS3/12-100
100%
7,4 A / 15,2 A
2 x 32A 400Vac (10x38)
(F1/F2)
1 separated output BAT 1
1 additional output +SP (before integrated distributor) for specific use, do not connect it directly to a
battery
Each output can be used on its own and supply the entire current.
100A/1425W
Type of charge selected using internal switch IU or IUoU
(Boost, Absorption, Floating – factory setting).
See selection wheel setting table. The chargers can operate on DC supply.
125A 150Vdc HRC 125LET (F3)
Rated conditions: from - 10°C to + 55 °C; over, de-rating : reduction of the output power < than 2,5
Casing comprises : Steel frame and steel front cover and Polycarbonate clasp
Protected with water-repellent varnish (marine environment)
NF EN61000-6-1, NF EN61000-6-2, NF EN61000-6-3, NF 61000-6-4
-
Against leaking input surges by rupture of VDR (voltage dependent resistor) (not covered by
warranty)
-
Against output polarity reversals by rupture of fuses
-
Against output short-circuits and surges
-
Against abnormal overheating by cutting off the charger (internal temperature probe 90°C),
Automatic re-start
Against output surges (17V ±5% for12V) (34V ±5% for 24V) (68V ±5% for 48V)
-
CPS3/24-120
from 85 to 265VAC single phase
75%
From 47 to 65Hz
16,8 A / 26,2 A
0,9 in rated conditions
> 80% in rated conditions
2 x 32A 400Vac (10x38)
(F1/F2)
120A/3420W
See selection wheel setting table
< 2% (in rated conditions)
< 2% (in rated conditions)
160A 150Vdc HRC 160LET
(F3)
%/°C up to 65°C
Continuous draft fans
Up to 70% (95% with no condensation)
-20°C to +70°C
Grey, black matt epoxy coating
350 x 400 x 123mm / 12,7Kg
328 x 292 mm
4 M5 round screws
IP22 (with cable glands)
NF EN60950, NF EN60335-2-29
CPS3/48-60
75%
15,2 A / 23 A
2 x 32A 400Vac (10x38)
(F1/F2)
60A/3420W
80A 150Vdc HRC
80LET (F3)
26