Parker PSE Serie Manuel D'utilisation page 19

Masquer les pouces Voir aussi pour PSE Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
5.3 Alarms/warnings
Touch
to enter on "alarms/warning" menu:
Touch "duration" to change the time of reserch.
Touch
to return to the previous menu.
When the nominal working conditions have been restored, some warn-
ing and alarm are automatically reset, for other alarms/warning it is nec-
essary to perform a manual reset.
Touch
to reset the alarm
Touch
to visualiza the historical alarms with:
the alarm code, the date, the number of alarms, the position in the se-
quence of occurrence, and the alarm activation time.
Touch
to return to the previous menu.
English
5.3.1 List of alarms/warnings
a = alarm
w = warning
aLD low dew point alarm
temperature B0<A9 for more than A10
seconds.
aLT
low evaporator
temperature B2<A12 for more than A13
temperature alarm
seconds
aHT2 high discharge
temperaure B8>A11
temperature alarm
aHP high pressure alarm
high pressure switch is tripped
aLP low pressure alarm
low pressure switch is tripped
aLTA low multicooter
temperature B4<A12 for more than A13
temperature alarm
seconds
aPI
Compressor thermal
compressor thermal protection is tripped
protection alarm
aPH phase monitoring alarm
phase monitoring relay is tripped
aCM1 communication expansion
the expansion 1 is not communicating
1 alarm
aCM2 communication expansion
the expansion 2 is not communicating
2 alarm
wB0 warning probe B0
probe broken or not connected
wB2 warning probe B2
probe broken or not connected
wB4 warning probe B4
probe broken or not connected
wB5 warning probe B5
probe broken or not connected
wB6 warning probe B6
probe broken or not connected
wB8 warning probe B8
probe broken or not connected
aFP1 high pressure transmitter
transmitter broken or not connected
P1 alarm
wHD high dew point warning
temperature B0>A6 for more than A8
minutes
wHT1 high discharge tempera-
temperature B8>A14 for more than A15
ture warning
minutes
wHP1 high pressure warning
pressure P1>A16 for more than 2 seconds
wHB5 high suction temperature
temperture B5>A18 for more than 1 minute
warning
wLP2 low pressure warning
pressure P2<A21 for more than 150 seconds
wSR Scheduled maintenance
the service time is elapsed
warning
wDR1 drain 1 warning
the condensate is not discharge from
cooler 1
wDR2 drain 2 warning
the condensate is not discharge from
cooler 2
wDR3 drain 3 warning
the condensate is not discharge from
cooler 3
aFP2 low pressure transmitter
transmitter broken or not connected
P2 alarm
PSE 460-1800
7/10

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pse460Pse520Pse630Pse750Pse900Pse1200 ... Afficher tout

Table des Matières