Lamborghini Caloreclima EM 16/M-E Notice D'installation Et D'entretien page 43

Masquer les pouces Voir aussi pour EM 16/M-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a drop in combustion air pres-
sure. It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure, checking that CO values do not
exceed 10,000 p.p.m..
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to shut it down if the gas pressure
falls below the minimum required level. This setting should be 40% lower than the gas pressure obtained with the burner
operating at maximum delivery.
CALIBRATION OF MAIMUM GAS PRESSURE SWITCH (ON REQUEST)
The maximum gas pressure switch locks-out the burner if the gas pressure is higher than the required level. Adjust the
pressure at the combustion head 15% (natural gas)/10% (B/P) higher than the rated output required at installation.
PRESSURE SWITCH
Type: LGW 10 A2P
GW 50 A5
GW 500 A5
Remove the cover and
adjust dial A
Air pressure switch
MODEL
EM 16/M-E
EM 26/M-E
CHECKING CONTROL BOX IONIZATION CURRENT
The minimum value of 3 μA should be observed,
and large oscillations are to be avoided.
P r e s s u r e
connector
Setting range mbars
DUNGS type
LGW 3 A2
0,4 - 3
- 43
Gas pressure switch
DUNGS type
GW 150 A5
GW 500 A5
MICROAMPEREMETER CONNECTION
-
Setting range mbars
5 - 120
100 - 500

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Em 26/m-e

Table des Matières