English
10.1 Fault signals
Code
Faults
no.
E04
Undervoltage
E05
Overvoltage
E10
Blocking
E11
Warning signal
Dry run
E21
Overload
E23
Short-circuit
E25
Contacting/
winding
E30
Module
overheat
E36
Module
defective
If the fault cannot be remedied, please consult the specialist
technician or the Wilo factory after-sales service.
11 Spare parts
Spare parts are ordered via local specialist retailers and/or Wilo
customer service.
In order to avoid queries and incorrect orders, all data on the
name plate should be submitted for each order.
20
Causes
Power supply too low
on mains side.
Power supply too
high on mains side.
Rotor blocked
Air in the pump
Sluggish motor
Motor current too
high
Winding defective
Module interior too
warm
Electronic compo-
nents defective
Remedies
Check mains voltage.
Check mains voltage.
Contact customer
service
Check water
quantity/pressure.
Contact customer
service
Contact customer
service
Contact customer
service
Check operating con-
ditions in chapter 5.2
Contact customer
service
WILO SE 05/2017