GAS BURNER CONTROL DEVICE GAS LME 21...
Operational status indication
Status
Waiting time «tw», other waiting states
Ignition phase, ignition controlled
Operation, flame o.k.
Operation, flame not o.k.
Extraneous light on burner startup
Undervoltage
Fault, alarm
Error code output (refer to «Error code table»)
Interface diagnostics
Legend
.... Steady on
After lockout. the red fault signa llamp will remaln steady on. In
thal conditio visual diagnostics of the cause of fault acccording to
the error code table can be activated by presslng the lockout reset
button for more than 3 seconds. Pressing the reset button again
for at least 3 seconds, interface diagnostics will be activated
The followlng sequence activates the diagnostics of Ihe cause of
fault:
Red blink code of signal lamp
(LED)
2 blinks
l l
3 x blinks
l l l
4 blinks
l l l l
5 blinks
l l l l l
6 blinks
l l l l l l
7 blinks
l l l l l l l
8 x blinks
l l l l l l l l
9 blinks
l l l l l l l l l
10 blinks
l l l l l l l l l l
During the time the cause of fault is diagnosed, the control outputs are deactivated
- Burner remains shut down
- External fault indication remains deactivated
- Fault status signal «AL» at terminal 10, according to the error code table
The diagnostics of the cause of fault is quit and the burner switched on again by resetting the burner
control. Press thelockout reset button for about 1 second (< 3 seconds).
During startup, status indication takes place according to the following table:
Color code table for multicolor signal lamp (LED)
Color code
......................................
¡.
l
¡
¡....................................................
n
¡
n
n
l
l
.....................................................
¡
Red
¡ Off
Error code table
«AL» at term. 10
Possible cause
No establishment of flame at the end of «TSA» -Faulty or soiled
fuel valves -Faulty or soiled flame detector -Poor adjustment of
On
burner, no fuel -Faulty ignition equipment
«LP» faulty -No or faulty air pressure signal after completion
On
«t10» - «LP» is welded in normal position
Extraneous light when burner startup
On
On
Time out «LP» - «LP» is welded in working position
On
Free
Too many losses of flame during operation (limitation of
On
repetitions) -Faulty or soiled fuel valves -Faulty or soiled flame
detector -Poor adjustment of burner
On
Free
On
Free
Off
Wiring error or internal error, output contacts, other faults
15 / 20
0006080895_200903
Color
Off
Flashing yellow
l
¡
l
¡
l
¡
l
Green
Flashing green
n
¡
n
¡
n
¡
n
Green-red
n
n
n
Yellow-red
l
l
l
Red
Flashing red
¡
¡
¡
Red flicker light
Yellow
Green
l
n
E
N
G
L
I
S
H