baltur BTG 15P Manuel D'installation, Utilisation Et Entretien page 38

Masquer les pouces Voir aussi pour BTG 15P:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LME 21... GAS BURNER CONTROL DEVICE
E
N
G
L
I
S
H
Legend
AL
Error message (alarm)
AS
Unit fuse
BV... Fuel valve
EK... Remote lockout reset button (internal)
ION
Ionization probe
FS
Flame signal
FSV Flame signal amplifier
GP
Gas pressure switch
H
Main switch
K1...5 Internal relays
LP
Air pressure switch
LR
Load controller
M
Fan motor
NT
Power supply
R
Control thermostat / pressurestat
SB
Safety limit thermostat
STB Safety limit thermostat
Si
External fuse
Equipment or
programmer
LME 21.430 A2 BT
Safety
Preventilation
time
time
s
s
3
40
t
Time
W
Limit thermostat / pressure switch
Z
Ignition transformer
A
Start command (switching on by «R»)
B-B´ Interval for establishment of flame
C
Operating position of burner reached
C-D
Burner operation (generation of heat)
D
Controlled shutdown by «R»
• Burner will immediately be shut down
• Burner control will immediately be ready for new startup
I
Cam I actuator
t1
Prepurge time
t3
Preignition time
t3n
Postignition time
t4
Interval between ignition «Off» and release of «BV2»
t10
Specified time for air pressure signal
TSA Ignition safety time
tw
Waiting time
Post
Opening time
Pre-
-
ignition
ignition
1st flame valve
and the 2nd flame valve
s
s
2
2
14 / 20
0006080895_200903
time travel
opening
damper
s
s
11
12
time travel
closing
damper
s
12

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Btg 20pBtg 28p

Table des Matières