Burner adjustment
The burner is factory-set as given in table 2. The burner can be set to a different power
by adjusting the pump pressure, nozzle, head and air setting as described in the follow-
ing paragraphs. In any case, the new power setting must come within the boiler's nominal
working range. After making any adjustments, use a combustion analyser to check that
the CO
% in the fumes is between 11% and 12%.
2
Table. 2 - Burner adjustment
Heating
Burner
Burner
capacity
model
capacity
US
kW
kg/h
Gall/h
30.1
SUN
2.54
0.65
Oil nozzle delivery table
table 3 indicates the oil deliveries (in kg/h) as the pump and nozzle pressure changes.
N.B. - The values given in the table are approximate, since the nozzle deliveries can vary
by ± 5%. Also, for burners with a preheater, the fuel flow rate decreases by approximately
10%.
Table. 3
Pump pressure kg/cm
NOZZLE
8
9
G.P.H.
0.40
1.36
1.44
0.50
1.70
1.80
0.60
2.04
2.16
0.65
2.21
2.34
0.75
2.55
2.70
0.85
2.89
3.06
1.00
3.40
3.61
Delivery at nozzle outlet in kg/h
Pump pressure adjustment
The pump pressure is factory set for optimum operation and should not normally be
changed. However, if special needs require a different pressure, after applying the pres-
sure gauge and lighting the burner turn the adjustment screw "6" indicated in fig. 26. It is
anyhow recommended to keep within the range of 10 - 14 bar
10
15
5
20
0
25
4
3
1
fig. 25 - SUNTEC pump
38
EN
Pump
Head
Nozzle
pressure
adjustment
Angle
Code
Bar
L
60°
35601320
10
22
2
10
11
12
13
1.52
1.59
1.67
1.73
1.90
1.99
2.08
2.17
2.28
2.39
2.50
2.60
2.47
2.59
2.71
2.82
2.85
2.99
3.12
3.25
3.23
3.39
3.54
3.68
3.80
m h
O
2
5
P
V
7
2
cod. 3540S756 - Rev. 01 - 03/2015
ATLAS D 30 K 100 UNIT
Air
adjustment
Mark
3
11
6
14
1.
Inlet (suction)
2.
Return
1.80
3.
Outlet to nozzle
2.25
4.
Pressure gauge connection
2.70
5.
Vacuum gauge connection
6.
Adjustment screw
2.92
7.
By-pass screw
3.37
Head and air shutter
3.82
Adjust the head and air flow rate according to the burner power as indicated in fig. 27
Turn the head adjustment screw B (fig. 28) clockwise or anticlockwise until the mark on
rod A (fig. 28) coincides with the pointer.
30
25
20
B
15
10
5
0
15.0
20.0
25.0
1,26
1,69
2,11
fig. 27 - Burner adjustments graph Prodotto_Gr1
A
Power
B
Adjustment pointer
C
Oil flow rate
6
"L" head (mm)
Air
To adjust the air flow, turn screw C (fig. 28) after loosening nut D. After making the ad-
justment, tighten nut D.
10
15
5
0
4
P
-
+
V
P
7
2
1
fig. 26 - DANFOSS pump
30.0
35.0
40.0
45.0
2,53
2,95
3,37
3,79
fig. 28 - Burner adjustment
20
25
m h
O
2
5
A (kW)
50.0
55.0
60.0
C (kg/h)
4,22
4,64
5,06