Installation and Operating Instructions
EN
+
NOTE
+
NOTE
Central ventilation units AIR1 XH
In order to use this function, at least one air quality sensor must be connected. The sensor-controlled operating function
can only be activated by the VOD timer.
Up to 3 different or same types of sensors can be connected to a ventilation unit with 3 free analogue inputs. The hig-
hest ventilation requirement has priority.
If a room temperature sensor is connected to analogue input AI2 (KWL-FTF temperature 0-10 V sensor), only analogue
inputs AI3 and AI4 will be available for the air quality sensors.
In order to connect more than 3 sensors to a ventilation unit, the optional signal converter AIR1-SK with 6 analogue
inputs and one analogue output is available. Only the same types of sensor can be connected per signal converter
AIR1-SK.
2 .3 .16 Closing the commissioning assistant
Select "YES" to start the ventilation application.
Complete configuration and
start application
No
The following settings must still be adjusted for operation after completing the commissioning assistant:
•
Time and date (see section 4.0.2 a)
•
Timer (see section 4.0.2)
2 .4
Emergency operation/Fire mode
If the potential-free switch contact DI2 is closed, the unit will switch to emergency operation/fire mode.
Access to the settings: Log on as Admin.
The emergency operation/fire mode settings can be found in the "Configuration" menu - "Fire protection":
• Operation during alarm (stopped, only supply air fan, only extract air fan, normal operation, continuous operation)
• Speed during fire alarm Supply air, Extract air
Fan stage during fire alarm ↑
SAF: 11 %
EAF: 7 %
Operat. when alarm stopped ↓
• Pressure Supply air/Extract air during fire alarm (-1 means no change to previous operation)
Pressure SAF/EAF
during fire alarm
SAF: -1 Pa
EAF: -1 Pa
A pre-set fan speed can be set for use in the event of a fire. This function is deactivated with "-1". The fire mode is
activated by closing the switch contact DI2.
Selection
Normally open
Normally closed
2 .5
Adjustment
The adjustment is carried out in the main menu after completing the commissioning assistant. It is carried out under the
submenu "Fan control".
Helios Ventilatoren
2019-XX-XX 09:30
System: Deactivated
Target: 19.5 Actual: 0.0 °C
Operating mode
Temperature
Fan control
Timer
Depending on the selected operating mode ("Constant volume flow", "Constant pressure", "Constant speed"), the
following settings can be adjusted:
a . Constant volume flow
• Volume flow regulation SAF (supply air fan)
• Boost xxx [m³/h]
• Normal xxx [m³/h]
• Reduced xxx [m³/h]
OK
OK
↑
OK
OK
↓
45
OK
OK
OK
OK
OK
OK
OK
OK