The power supply must comply with the following table:
M.P.I.-100M
Voltage
230 V 1ph
Power cable
3 x 2.5 mm²
cross section
max electric current
13 A
requirement
Electrical protection
16 A
5.1
Electrical panel side
The line supplying the heat pump must be configured and fitted with one or more devices for:
•
proper earthing of the machine
•
protection of people by means of a 30 mA residual current device (interrupter or circuit breaker) dedicated
to the pool electric panel or specific to the heat pump line (unless the house is already equipped with one)
•
protection of the machine against "overloads" and short-circuits by means of a thermal magnetic circuit-
breaker
To avoid the untimely tripping of the circuit breakers on starting up the machine, use D curve circuit breakers.
5.2
Heat pump side
The machine is wired in by means of the white connection box beside the information plate.
•
Remove the protective casing from the heat exchanger.
•
Withdraw the 4 plastic screws from the lid of the connection box to release and remove the lid.
•
Feed the power cable into the box, pushing them up through the cable glands located in the bottom.
•
Strip the 1 cm of each wire, and connect these to the domino, taking care to respect the live, neutral and
earth phases.
•
Tighten the cable gland nuts to immobilise the cable and ensure that the seal around the cable is leak tight.
• Replace the lid and screws, then replace the heat exchanger casing.
Single phase
Black wire = live
Blue wire = neutral
Yellow/green wire = earth
38/96
2020/11 - Indice de révision : I - Code : 33340
M.P.I.-160M
M.P.I.-190M
230 V 1ph
230 V 1ph
3 x 4 mm²
3 x 6 mm²
19 A
28 A
25 A
32 A
M.P.I.-190T
M.P.I.-240M
400 V 3ph
230 V 1ph
5 x 2.5 mm²
3 x 6 mm²
13 A
29.5 A
16 A
40 A
Three phase
Black wire = live 1
Brown wire = live 2
Grey wire = live 3
Blue wire = neutral
Yellow/green wire = earth
CHAUFFAGE & DÉSHUMIDIFICATION
M.P.I.-240T
M.P.I.-320T
400 V 3ph
400 V 3ph
5 x 2.5 mm²
5 x 4 mm²
13 A
19 A
16 A
32 A
M.P.I.-380T
400 V 3ph
5 x 4 mm²
21 A
32 A