Installation instructions, for professionals only
8. Commissioning
8.1. Setting the function selector switch
The function selection switch in the
low-voltage connection area allows
a variety of product functions to be
activated. The figure at the right
shows the standard setting for the
function selection switch.
Note that the control unit needs to
be switched off for 10 seconds after
making changes so that the settings
are saved.
Setting the heating time limit
The maximum heating time is set to 6 hours as
standard. The sauna control unit shuts down
automatically after the maximum heating time
for safety reasons.
The function selection switch in the low-voltage
connection area allows the maximum heat-
ing period to be set to 12 hours,18 hours or
24 hours. The required positions of the func-
tion selection switch can be found in the table
on the right.
!
EN 60335-2-53 specifies a maximum heating time limit of 6 hours for
private saunas. For saunas in hotels, apartment blocks and similar
locations, a maximum heating time limit of 12 hours is permissible.
Extending the heating time limit to 18 hours or 24 hours is only permit-
ted in public saunas.