Quick SBC ADVANCED Série Manuel De L'utilisateur page 14

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

INSTALLATION
GB
EQUIPMENT SUPPLY
The equipment already includes a power cable for AC supply. For connections to an AC supply see
fig.2. Before powering up the battery charger check that the power supply voltage, described on the
rating label, corresponds to that supplied by the AC supply source.
In the electrical circuit a two-pole switch must be installed for the sole use of switching the equip-
ment ON & OFF.
The insulation between the contact points of the connections of the AC supply must be at least 3 mm.
The connections to the AC supply must be carried out according to local electrical codes.
WARNING: before connecting or disconnecting the cables from the electrical terminals of the bat-
tery charger, make sure that the equipment is disconnected from the AC mains and the batteries.
WARNING: in cases where the power cable could be damaged, have this changed by a "Quick"
service centre. In order to avoid accidents, the equipment must only be opened by authorised
personnel.
FIG.2
5 cm
5 cm
5 cm
BATTERY
WARNING: during charge, batteries can generate explosive gases, therefore avoid sparks or
naked flames. Provide adequate ventilation to the battery area whilst charging.
WARNING: before connecting the batteries check the terminals of the cables from the bat-
tery. Reversing the terminals could seriously damage the battery charger even if protected by
fuses.
The positive terminal of the battery or of the group of batteries must be connected to one of the posi-
tive terminals of the battery charger. The negative terminal of the battery or of the group of batteries
must be connected to the negative terminal of the battery charger. To make the connections use the
cable terminals supplied with the equipment.
14
SLAVE A MASTER
Battery switches
battery
n° 2
battery
n° 1
Blue
Neutral
Yellow
Earth
Green
Live
Brown