Operating Conditions; Operating And Display Elements - Rittal CMC III CAN-Bus DRC Notice D'installation Et Notice D'utilisation Succincte

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.4

Operating conditions

The CAN bus DRC may only be operated under the following operating conditions:
Temperature operational range:
Humidity operational range:
Degree of protection:
4
Assembly
4.1
Assembly instructions
The assembly of the CAN bus DRC is made as shown in fig. 2.
5
Installation and operation
5.1

Operating and display elements

The operating and display elements are shown in fig. 3.
Key for fig. 3
1
"C" key (no function)
2
Multi-LED for the status display
3
24 V
power supply (direct connection)
4
Connection for CMC-TC "RFID controller" unit RJ 45
5
Not assigned
6
CAN bus connection
7
CAN bus connection
5.2
Installation
Note:
The power pack (7030.060) must always be connected to the voltage input of the CAN
bus DRC.
Note:
The unit is free from power only after all power sources have been disconnected!
Please connect all CMC-TC "RFID controller" units (7890.500) to the appropriate connection
(fig. 3, item 4).
Connect the CAN bus DRC with a CAN bus connection cable to the CMC III PU or to the neigh-
bouring elements on the CAN bus (fig. 3, item 6, 7). A maximum of two CAN-Bus DRCs may be
connected to one CAN-Bus.
Note:
If the RFID controller is connected to the CAN-Bus DRC retrospectively, please make
sure you disconnect the CAN-Bus DRC first before connecting it again later.
Display of the status change:
– The two green and the two red CAN bus LEDs on the CAN bus connection flash.
– The multi-LED of the Processing Unit flashes continually in the green – orange – red sequence.
Rittal CMC III CAN-Bus DRC
+0°C...+55°C
5%...95% relative humidity, non-condensing
IP 30 in accordance with EN 60 529
, 24 V
, 24 V
Assembly, Installation and operation
EN
7