SinePower
10
Troubleshooting
!
WARNING!
Do not open the device. You risk sustaining an electric shock by doing
this.
I
NOTE
If you have detailed questions on the specifications of the inverter
please contact the manufacturer (addresses on the back of the instruc-
tion manual).
The LED (fig. 2 2, page 3) indicates the fault:
LED display
Cause
Quick flash
Input voltage is too high Check the input voltage and reduce it.
Input voltage too low
Long flash, short
Overheating
interruption
Excessive load
Off
Other fault
EN
Remedy
The battery needs recharging.
Check the cables and connections.
Switch off the inverter and the consumer.
Wait 5 to 10 minutes and switch the inverter
on again without any electric consumers.
Reduce the load and make sure the inverter
has better ventilation. Then switch the con-
sumer back on.
Switch off the inverter and remove the
consumer.
Then switch the inverter back on without the
consumer. If no excessive load is now shown,
then there is a short circuit in the consumer or
the total load was higher than the power
specified on the data sheet.
Check the cables and connections.
Contact the service.
Troubleshooting