SUPPLEMENT
Case 3A
Automatic Address Setting in Heating Mode
● Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic Address Setting from Outdoor Unit
Case 2
1.
Perform steps 1 – 4 in the same way as for
.
5.
Turn the indoor and outdoor unit power ON at all systems.
6.
To perform automatic address setting in
Heating mode
you wish to set the addresses, short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than one
system at the same time.)
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Heating
mode begins.)
(All indoor units operate.)
* To cancel, again short-circuit the automatic address pin (CN054) for 1 second or longer, then release it. The LED
that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to perform
automatic address setting again.
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the main unit control PCB turn OFF.)
7.
At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN054) for 1 second or longer, then
release it.
(Repeat the same steps to complete automatic address setting for all units.)
8.
Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 – 5, then use the remote controller and
complete automatic address setting.
● Refer to "Automatic Address Setting from Remote Controller."
, on the outdoor main unit control PCB in the refrigerant system where
47
Case 3B
Automatic Address Setting in Cooling Mode
● Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.
Automatic Address Setting from Outdoor Unit
Case 2
1.
Perform steps 1 – 4 in the same way as for
.
5.
Turn the indoor and outdoor unit power ON at all systems.
6.
To perform automatic address setting in
Cooling mode
you wish to set the addresses, short-circuit the mode change 2P pin (CN085). At the same time, short-circuit the automatic
address pin (CN054) for 1 second or longer, then release it. (Be sure to perform this process for one system at a time. Automatic
address settings cannot be performed for more than one system at the same time.)
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling
mode begins.)
(All indoor units operate.)
* To cancel, again short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor main unit control PCB turn
OFF.)
7.
At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN054) for 1 second or longer, then
release it.
(Repeat the same steps to complete automatic address setting for all units.)
8.
Operation from the remote controllers is now possible.
* Automatic address setting in Cooling mode cannot be done from the remote controller.
Automatic Address Setting* from the Remote Controller
Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code "A1"
1. Press the remote controller timer time
button and
button at the
same time. (Press and hold for 4 seconds or longer.)
2. Next, press either the temperature setting
or
button.
(Check that the item code is "A1.")
3. Use either the
or
button to set the system No. to perform
automatic address setting.
4. Then press the
button.
(Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the
system returns to normal stopped status.) <Approximately 4 – 5 minutes
is required.> (During automatic address setting, "
SETTING
" is displayed on
the remote controller. This message disappears when automatic address
setting is completed.)
5. Repeat the same steps to perform automatic address setting for each
successive system.
, on the outdoor main unit control PCB in the refrigerant system where