8.3 Technical data
Electrical
supply inlet
Model
230/1/60
PST 090
230/3/60
460/3/60
230/3/60
460/3/60
230/3/60
PST 130
460/3/60
230/3/60
PST 150
460/3/60
230/3/60
PST 175
460/3/60
230/3/60
PST 250
460/3/60
230/3/60
PST 280
460/3/60
230/3/60
PST 340
460/3/60
Calibration values
Hot gas valve
66.7 - 69.6 PSIg
PST 090-340
4.6 - 4.8 barg
(*) Models for Canada with CRN, max working pressure is:
174 PSIg (12 bar).
Compressor
1
MC1(AC/Wc)
RLA
LRA
RLA
(A)
(A)
(A)
8.9
36
0.6
7.1
38
0.6
3.3
16
0.6
7.1
38
0.61
3.3
20
0.61
7.1
38
0.61
3.3
20
0.61
7.9
45
0.61
4.2
23
0.61
10
63
0.61
5
31
0.61
13.9
88
2.2
6.4
44
1.25
13.9
88
2.2
6.4
44
1.25
-
-
7.9
50
1.25
Fan pressure Switch
9-HGV
12-PV
ON: 261 PSIg
OFF: 203 PSIg
ON: 18 bar
OFF: 14 bar
PST 090-340
Fan motor
Minimum circuit ampacity
3
MCA(Ac)
EV1 (Ac)
(HP)
(A)
0.13
11.7
0.13
9.4
0.13
4.6
0.59
8.9
0.59
4.8
0.59
8.9
0.59
4.8
0.59
9.9
0.59
5.6
0.59
12.5
0.59
7.0
1.07
19.5
1.07
9.3
1.07
19.5
1.07
9.3
-
-
-
1.07
11.1
High pressure switch
Low pressure switch
15-HP
406 PSIg
28 barg
Maximum protection
device rating
MCA(Wc)
HACR(Ac)
(A)
(A)
-
15
-
15
-
10
-
10
-
6
-
10
-
6
-
15
-
10
-
15
-
10
17.4
20
8.0
15
17.4
20
8.0
15
-
-
9.9
15
Water pressostatic valve
6-LP
22-WPV
21.8 - 36.3 PSIg
232 PSIg
1.5 - 2.5 barg
16 barg
6
Minimum section
validated cable for
HACR(Wc)
electrical
connections
Ø
(A)
-
12AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
20
12AWG
15
12AWG
20
12AWG
15
12AWG
-
-
15
12AWG
Air - Side Max
Working Pressure
203 PSIg(*)
14 bar(*)

Publicité

Table des Matières