12. Function
Trigger the flow of water
12.1 Press the pressure cap.
• The water will flow.
• The water flow stops automatically once the preset flow time has expired.
☞
The flow time is adjustable from 1 - 50 seconds.
Temperature selection
13. Adjusting the flow time
13.1 Set the desired temperature of the mixed water.
13.2 Remove the cover platelet.
13.3 Use a screwdriver to set the flow time.
+ longer flow time (max. 50 s)
– shorter flow time (min. 1 s)
13.4 Trigger the fitting to measure the flow time.
13.5 Once the desired flow time has been set, put the cover plate place.
14. Thermal disinfection -manual-
This shower fitting offers thermal disinfection to reduce the risk of a legionella
infection.
The thermal disinfection process is triggered by overturning the thermostat.
Warning!
Personal protective measures (scald protection) must be implemented for the
duration of the thermal disinfection. This might include cordoning off the shower
facilities.
Failure to observe this instruction can result in injuries due to scalding.
The operator is responsible for the execution, monitoring, and logging (room,
tapping point, date, time, temperature and duration).
The manufacturer does not accept any liability for claims by third parties relating to
the improper execution of thermal disinfection on the part of the operator.
The thermostat fitting has been prepared to carry out a thermal disinfection process
when the thermostat is overturned. The thermostat fitting can be manually thermally
disinfected (flushed with water at a temperature of 70°C) by unlocking the covered
stop on the temperature selector.
- 7 -