Testing Phase Sequence - Beha-Amprobe Telaris Série Guide D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 68
To measure earth resistance:
1. Turn the rotary switch to the
2. Press and release
• The primary (upper) display shows the earth resistance reading.
• Voltage detected between the test rods will be displayed in the secondary display. If
greater than 10 V, the test is inhibited.
• If the measurement is too noisy, Err 5 will be displayed. (The measured value accuracy
is degraded by the noise). Press the down arrow (
Press the up arrow (
• If the probe resistance is too high, Err 6 is displayed. Probe resistance may be reduced by
driving the test stakes further into the earth or wetting the earth around the test stakes.

Testing Phase Sequence

Figure 21. Phase Sequence Display/Switch and Terminal Settings
Use the connection shown in Figure 22 for a phase sequence test connection.
62% L
L
Figure 20. Earth Resistance Test Connection
position.
. Wait for the test to complete.
) to return to the Err 5 display.
N (L3/Blue)
L (L1/Red)
Figure 22. Phase Sequence Test Connection
) to display the measured value.
PE (L2/Green)
19
L1
L2
L3

Publicité

Table des Matières
loading

Table des Matières