3 Transport and interim storage
When receiving the material, check that there has
been no damage during the transport. If shipping
damage has occurred, take all necessary steps with
the carrier within the allowed time.
CAUTION! Outside influences may cause damages
If the delivered material is to be installed later on,
store it in a dry place and protect it from impacts
and any outside influences (humidity, frost etc.).
Handle the pump carefully so as not to damage the
unit prior to installation.
4 Intended use (Application)
CAUTION! Possible damage of the pump
These pumps are intended for use with water only
This pump's basic function is to pump warm or cold
water or other low viscosity fluids that contain no
mineral oil, abrasive substances or materials having
long fibres. The manufacturer's approval is required
for use to pump corrosive chemicals.
Application areas:
• water distribution and boosting installations
• industrial circulation systems
• process fluids
• cooling water circuits
• fire-fighting and washing stations
• watering installations, etc.
Outline and pipe dimensions (see: Fig. 2)
Types
MVIS15-02 to MVIS15-08
MVIS30-02 to MVIS30-06
MVIS50-02 to MVIS50-03
Types
MVIS15-02 to MVIS15-08
MVIS30-02 to MVIS30-06
MVIS50-02 to MVIS50-03

5.3 Scope of Supply

• Complete pump and motor, NPT companion flanges,
bolts and flange gaskets
• Installation and operating instructions
4
Dimensions (inch)
A
B
C
D
E
15
1
3
7
8
/
/
16
16
15
1
3
/
7
/
8
16
16
1
5
10
10
/
8
Dimensions (mm)
A
B
C
D
E
100
180
157
212
204
100
180
157
212
204
130
215
187
252
250
5 Technical data
5.1 Type key
Example: MVIS15-02-1/O/K/3-460-60-2
MVIS
Pump family
15
Nominal flow rate in GPM at 60Hz / 2 poles
- 02
Number of stages
- 1
1 = Stainless steel 304
/ O
O = Oval flange 250 # with NPT companion flange
/ E
E = EPDM o'ring
/ 3
3 = Three phase
- 460
230 = 208-230 V
460 = 460 V
575 = 575 V
- 60
60 = 60 HZ
- 2
2 = 2 poles
5.2

Data table

Maximum operating pressure
Pump casing:
Maximum suction pressure:
Temperature range
Liquid temperatures
Ambient temperature
Electrical data
Motor Protection class:
Insulation class:
Frequency
Voltages
Others
Minimum suction head:
Ambient humidity:
F
H
K
L
3
2
15-22
6
/
4
3
2
16-20
/
6
4
1
1
3
3
17-20
7
/
/
/
8
16
4
F
H
K
L
50
378-548
20
160
50
398-500
20
160
80
425-485
20
200
230 PSI (16 bar)
140 PSI (10 bar)
14°F to 122°F
(- 10° to + 50 °C)
+104°F Max (+ 40 °C)
NEMA 2
H
60 Hz
3
: 208-230 V, 460 V, 575 V
~
(± 10 %)
3 ft (1 m)
<90 %
R
S
T
3
NPT 1"
3
Ø ½
/
8
3
/
NPT 1"¼
3
Ø ½
8
7
NPT 1"½
4
Ø ½
/
8
R
S
T
NPT 1"
75
Ø12
NPT 1"¼
75
Ø12
NPT 1"½
100
Ø 12
WILO SE 03/2009
U
M10
M10
M12
U
M10
M10
M12