Connecting The Power Cables; Connecting The Power Cables For The Tscs 12Xx Models - Tectro TS 1225 Manuel D'installation

Masquer les pouces Voir aussi pour TS 1225:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 32
Model
≤ 3,5 kW
> 3,5 kW
G
ATTENTION!
The supply voltage must be according the rated voltage of the air conditioning

11. CONNECTING THE POWER CABLES

11.1 Connecting the power cables for the TSCS 12xx models.

a.
A power cable with a length of 4.0 meter for the electrical connection between indoor and outdoor
unit is supplied with the device and can be found in the packaging of the refrigerant piping (indoor
unit).
b.
This electrical cable is supplied with an electrical push fit coupling.
c.
This electrical cable is supplied with an electrical push fit coupling.
d.
Remove the cover plate of the terminal block of the outdoor unit by unscrewing the screw.
e.
Click the connector of the indoor unit into the connector of the outdoor unit and secure the cable
on the connector block with the mounted cable clamp.
f.
Connect the power cable only when the entire installation of the air conditioner is completed.
G
ATTENTION
Insert the plug in a socket for models with a capacity < 4.5 kW.
Connect the power cable directly to the mains for models with a capacity > 4.5 kW Do not use a
plug and socket. The high current can damage the pins of the plug and the socket and cause fire.
4
86
Rated input current
Mains
220 - 240V, ~50Hz
220 - 240V, ~50Hz
Cover plate
Picture 17
Diameter power cord
(switch/fuse)
16A
16A slow
2,5 mm
2
2,5 mm
2