LCD Setting

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "SELECT"
button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to
exit.
Setting Programs:
Program
Description
00
Exit setting mode
02
Output voltage
03
Output frequency
Maximum utility charging
04
current
Bulk charging voltage
05
(C.V voltage)
06
Floating charging voltage
07
Low DC cut-off voltage
Power saving mode
09
enable/disable
16
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 18 AA 59 203 14
Selectable option
Escape
220V (default)
240V
50Hz (default)
2A
20A
40A
60A
Default setting: 56.4V
This program can be set up. Setting range is from 48.0V to
58.4V for 48V model. Each click increment 0.1V.
Default setting: 54V
This program can be set up. Setting range is from 48.0V to
58.4V for 48V model. Each click increment 0.1V.
Default setting: 42V
This program can be set up. Setting range is from 40.0V to
48.0V for 48V model. Each click increment 0.1V. Low DC
cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
Saving mode disable
(default)
230V
60Hz
10A (default)
30A
50A
If disabled, no matter connected load
is low or high, the output (on/off
status) of inverter will not be affected.