SPECIFICATIONS

Table 1 Line Mode Specifications
Input Voltage Waveform
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage
Nominal Input Frequency
Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
*
*Transfer time may be longer than specified figure when the unit is operating in parallel system.
Table 2 Inverter Mode Specifications
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Efficiency
Overload Protection
Surge Capacity
Nominal DC Input Voltage
Cold Start Voltage
Low DC Warning Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Warning Return Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
High DC Recovery Voltage
High DC Cut-off Voltage
No Load Power Consumption
Saving Mode Power Consumption
21
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 18 AA 59 203 14
Sinusoidal (utility or generator)
50Hz / 60Hz (Auto detection)
Line mode: Circuit Breaker; Battery mode: Electronic Circuits
>97% ( Rated R load, battery full charged )
Pure Sine Wave
5s@≥150% load; 10s@110%~150% load
2* rated power for 5 seconds
220Vac
170Vac±3V
180Vac±3V
255Vac±3V
245Vac±3V
300Vac
47.5±1Hz
48±1Hz
52.5±1Hz
52±1Hz
10ms typical
5KVA/5KW
220Vac±5%
60Hz or 50Hz
90%
48Vdc
46.0Vdc
44.0Vdc
42.8Vdc
40.4Vdc
46.0Vdc
44.8Vdc
42.4Vdc
42.0Vdc
40.8Vdc
38.4Vdc
58Vdc
60Vdc
<50W
<15W