Charging Curve - INFOSEC G1 Manuel Utilisateur

Convertisseur chargeur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 3 Charge Mode Specifications
Charging Current (UPS)
Default: 30A, Max.: 60A
@ Nominal Input Voltage
Bulk Charging Voltage
56.4Vdc
Floating Charging Voltage
54Vdc
Charging Algorithm
3-Step
Battery Voltage, per cell
Charging Current, %
2.43Vdc (2.35Vdc)
Voltage
2.25Vdc
100%

Charging Curve

50%
T1 = 10* T0, minimum 10mins, maximum 8hrs
Current
Time
Bulk
Absorption
Maintenance
(Constant Current)
(Constant Voltage)
(Floating)
Table 4 General Specifications
Safety Certification
CE RoHS
Operating Temperature Range
0°C to 40°C
Storage temperature
-15°C~ 60°C
Dimension (D*W*H), mm
400 x 438 x 86.3
Net Weight, kg
9.1
22
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 18 AA 59 203 14