Connection guidelines
- The appliance must be supplied with 230V 50 Hz.
- The appliance must be directly connected to the mains downstream
of the omnipolar cut-off device in accordance with installation
guidelines. A 3-wire cable (Brown = Phase, Blue = Neutral, Black =
Pilot wire) is used to connect to the supply circuit through a junction
box.
- In humid rooms, such as kitchens and bathrooms, the junction box
must be installed at least 25 cm from the ground. The installation
must be equipped with a 30mA residual-current circuit-breaker
protective device.
- Connection to ground is prohibited. Do not connect the pilot wire
(black) to ground.
- If the power cable is damaged, it must be replaced by the
manufacturer, their after sales department or by a similarly qualified
person, in order to avoid any danger.
- If the control or controlled device is protected by a 30mA residual-
current circuit-breaker protective device (e.g. in the bathroom) then
the power supply for the pilot wire on this differential needs to be
protected.
Drill points B
Drill points A
CONNECTING THE APPLIANCE
Panel heater cable
Phase=brown
Neutral=blue
Pilot wire=Black
1st case: only one heater
2nd case: Slave heater
PHASE
Electricity
grid
NEUTRAL
Three possible cases
The pilot wire end is insulated
and not further connected
To the appliance with cassette or
programming unit.
25
Power
750W
1000W
1250W
1500W
2000W