System cover with sleeve method
HSI150 MA... (HSI90 MA...)
18 Assembly
1
In the first layer, place the spacers directly on the soil
and clip in the hose (distance between spacers: ap-
prox. 1.5 m).
2
Fill up space between and next to the pipes and com-
press.
3
In the case of multi-layer hose systems, the spacers
are placed on the layer of hoses immediately below.
The hoses can then be clipped in again.
4
>Proceed with additional layers in the same way as
with the previous ones.
► For further information, see "Installation instructions
for Hateflex hose systems".
19 Connection of Hateflex hose systems to
shafts and stations
Hauff cable entries (HSI 90/HSI 150) are available for
connecting Hateflex hose systems to shafts and stations.
Rubber-mounted pipe connection sleeves are available as
pipe connection systems for all pipe diameters of the Ha-
teflex hose systems.
The following factors determine the potential feed
lengths:
Cable (type/weight/flexibility)
■
Route layout (height profile)
■
Number/position/radiuses of curves/imprecisions
■
Friction coefficient (cable/pipe wall)
■
Lubricant (type/quantity)
■
■
Feed method and speed (also surface temperature)
Ratio of internal pipe diameter to cable diameter
■
Quality of installation, e.g.
■
pipe support/compression of embedding ma-
□
terial = influence on pipe deformation,
filling/compression of embedding around pipe
□
bends/curves = important for taking mechani-
cal load when feeding in cables.
Service telephone + 49 7322 1333-0
Subject to change!
Réf. art. : 5090030031 Rév. : 01/2021-02-22
EN
21