TEST AND MAINTENANCE PLAN

The following must be checked:
Interval
Test and maintenance work
Test run up to maximum nominal speed
1/2 annual
and then deactivate again
Check fan and drive motor for running noises.
1/2 annual
Test run for at least 20 minutes and then deactivate
again.
For fans with bearing condition diagnostics, operate fan
Annual
until steady-state is reached (around 60-75 minutes) be-
fore reading out values (see Installation and Operating
Instructions for LZD).
General visual inspection and check of fan condition for
external contamination, correct fastening, corrosion and
Annual
damage.
Clean components for functional integrity if needed.
Check fan suspension and on-site substructure/founda-
tion for damage and corrosion as well as correct
Annual
fastening.
Check flexible connectors and connections for tension-
free installation, tightness, correct fastening, contamina-
Annual
tion and damage.
Clean components for functional integrity if needed.
Check vibration dampers for functionality, correct faste-
Annual
ning, corrosion and damage.
Check air gap between wingtip and fan casing.
Annual
Check drive motor for contamination, corrosion, damage
and correct fastening. Clean components for functional
Annual
integrity if needed.
Check impeller for contamination, corrosion, damage
and correct fastening.
Annual
Clean components for functional integrity if needed.
Check inspection opening for tight fit, corrosion and
Annual
damage.
Check protection devices (protection grilles, etc.) for
contamination, corrosion, damage and correct fastening.
Annual
Clean components for functional integrity if needed.
Check accessory components (mounting brackets,
backdraught shutters, extension ducts, etc.) for conta-
mination, corrosion, damage and correct fastening.
Annual
Clean components for functional integrity if needed.
Check terminal box (motor and casing terminal box)
and connection cable for correct fit, damage and cor-
Annual
rosion.
With regard to smoke exhaust fans with separate co-
oling air fans, check the function and unhindered cooling
Annual
air flow and remove any contaminants in the cross sec-
tion.
Annual
Check power consumption of drive motor
Check motor protection device, for ventilation mode
Annual
(motor protection device, not in case of fire).
Check on-site bridging of frequency converter and mo-
Annual
tor protection devices in case of fire.
Measurement and evaluation of bearing conditions with
Annual
bearing condition diagnostics.
Check fan vibration state
Annual
Check impeller for imbalance
Annual
Smoke Exhaust Fans F300/F400/F600 – B AVD and B VAR
Standard
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
24
Fan
incl . LZD Basic
incl . LZD Comfort
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
To be carried out by:
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Instructed personnel
Specialist personnel
Specialist personnel