Installation and Operation Instructions
CHAPTER 5
CLEANING AND
MAINTENANCE
CHAPTER 6
INDICATIONS –
DISTURBANCE ORIGINS
MiniVent M1/100 P/120 P
5.0

Cleaning and maintenance

- Before cleaning, ensure that the fan is isolated from the power supply.
- Prevent unintentional restart!
- Clean device only with a damp cloth.
- The device is maintenance-free.
5.1
Dismantling of facia
Procedure:
1. Isolate the device from the power supply and prevent unintentional restart!
2. Remove the facia
by applying light pressure on the spring catches left and right of the facia (Fig.12).
3. Unfasten the screws of the control board cover
fig.12
Remove the facia by
applying light pressu-
re on the spring
catches left and
right of the facia)
6.0
Indications – Disturbance origins
- If the thermal protection trips this could be the result of dirt build-up, a hard running impeller and/or bearings.
Too high winding temperature through insufficient motor cooling, or too high air flow temperature could be the
cause of disturbance.
- Abnormal noises can mean worn out bearings.
- Vibrations can originate from an unbalanced or dirty impeller or due to the installation.
- Extreme performance reduction can occur if the fan must work against too high resistance of the ventilation system
or if there is a lack of sufficient supply air (causing also higher sound level).
(Fig.13).
fig.13