9.5. Selecting the external static pressure
As the factory setting is for use under an external static pressure of 0.20 in. WG (50
Pa), no switch operation is needed when using under the standard condition.
External static pressure
0.14 in. WG
(35 Pa)
0.20 in. WG
(50 Pa)
0.28 in. WG
(70 Pa)
0.4 in. WG
(100 Pa)
0.60 in. WG
(150 Pa)
[Fig. 9.5.1] (P.5)
<Indoor controller board>
9.6. Setting addresses
(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P.5)
<Indoor controller board>
•
There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11(for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
The branch number assigned to each indoor unit is the port number of the
BC controller to which the indoor unit is connected.
Leave it to "0" on the non-R2 series of units.
•
The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
•
The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
9.9. Electrical characteristics
Model
Hz
PEFY-P06NMAU-E2
PEFY-P08NMAU-E2
PEFY-P12NMAU-E2
PEFY-P15NMAU-E2
PEFY-P18NMAU-E2
PEFY-P24NMAU-E2
60 Hz
PEFY-P27NMAU-E2
PEFY-P30NMAU-E2
PEFY-P36NMAU-E2
PEFY-P48NMAU-E2
PEFY-P54NMAU-E2
9.7. Sensing room temperature with the
Switch operation
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
3
1
necessary also makes it possible to adjust the air flow at a time when the heating
2
2
1
thermometer is OFF.
SWA
SWC
3
9.8. Changing the power voltage setting
1
2
2
1
(Be sure to operate with the main power turned OFF.)
SWA
SWC
Please set the switch SW5 according to the power voltage.
3
1
•
2
2
•
1
SWA
SWC
3
1
2
2
1
SWA
SWC
3
1
2
2
1
SWA
SWC
Symbols : MCA : Max. Circuit Amps ( = 1.25 × FLA) FLA : Full Load Amps
IFM : Indoor Fan Motor
Indoor Unit
Volts
Voltage range
MCA (A)
1.05 / 1.05
1.05 / 1.05
1.20 / 1.20
1.45 / 1.45
1.56 / 1.56
208 / 230 V
188 to 253 V
2.73 / 2.73
2.73 / 2.73
2.73 / 2.73
3.32 / 3.32
3.41 / 3.41
3.31 / 3.31
built-in sensor in a remote controller
[Fig. 9.5.1] (P.5)
Set SW5 to 240V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 220V side.
Output : Fan motor rated output
IFM
Output (kW)
FLA (A)
0.085 / 0.085
0.84 / 0.84
0.085 / 0.085
0.84 / 0.84
0.085 / 0.085
0.96 / 0.96
0.085 / 0.085
1.16 / 1.16
0.085 / 0.085
1.25 / 1.25
0.121 / 0.121
2.18 / 2.18
0.121 / 0.121
2.18 / 2.18
0.121 / 0.121
2.18 / 2.18
0.244 / 0.244
2.66 / 2.66
0.244 / 0.244
2.73 / 2.73
0.244 / 0.244
2.65 / 2.65