LoRaWAN Smart Building COMFORT - Guide utilisateur / User guide version V2.1.1
Explanation of thresholds and hysteresis:
FR
EN
The parameters associated with this operating mode are:
•
The transmission period (equal to zero in this use case) (register 301).
•
The acquisition period (register 321)
•
The high alarm threshold for the temperature sensor (register 331).
•
The high alarm hysteresis for the temperature sensor (register 332)
•
The low alarm threshold for the temperature sensor (register 333).
•
The low alarm hysteresis for the temperature sensor (register 334).
•
The high alarm threshold for the humidity sensor (register 341).
•
The high alarm hysteresis for the humidity sensor (register 342).
•
The low alarm threshold for the humidity sensor (register 343).
•
The low alarm threshold for the humidity sensor (register 344).
High alarm enabling
Low alarm enabling
High alarm disabling
High threshold
High threshold -
high threshold hysteresis
Sensor value
Low threshold +
low threshold hysteresis
Low threshold
Low alarm disabling
Page
46